11 Troubleshooting

Installer and user reference guide

34

LRMEQ+4BY1

Air-cooled refrigeration condensing unit

4P500362-1A – 2018.09

DANGER: RISK OF ELECTROCUTION

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out:  power  to  this  appliance  MUST  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

DANGER: RISK OF BURNING

11.3

Solving problems based on error
codes

INFORMATION

When a malfunction occurs, X3M outputs a caution (C/C1)
or  warning  (C/W1)  signal,  and  the  H2P  LED  on  the  main
PCB lights up.

You can display the error codes of the 3 latest malfunctions by using
the  push  buttons  and  7‑LEDs  display  (see 

"7.2.3  Field  setting

components"  on  page  28

).  Error  codes  consist  of  2  characters

(example: E3).

After solving the problem, reset the malfunction by turning OFF and
ON the operation switch, and retry operation.

11.3.1

To display the error codes of the latest
malfunctions

#

Action

Display

1

Start from the default
situation.

2

Select mode 1.

BS1

[1×]

#

Action

Display

3

Select a malfunction.

("X×" depends on the
setting that you want
to select.)

BS2

[X×]

Possible malfunctions:

[1‑14] Latest malfunction:

[1‑15] 2nd last malfunction:

[1‑16] 3rd last malfunction:

4

Display the 

first

character

 of the error

code.

BS3

[1×]

Possible characters:

E: 

H: 

F: 

J: 

L: 

P: 

U: 

5

Display the 

second

character

 of the error

code.

BS2

[1×]

Possible characters:

1: 

2: 

3: 

4: 

5: 

6: 

7: 

8: 

9: 

A: 

C: 

6

Quit mode 1.

BS1

[1×]

11.3.2

Error codes: Overview

Code

Description

Criteria

Times of

retry

Output signal

Cause

Solution

Abnormally high pressure level

High pressure switch ≥4.0 MPa (40 bar)

0

Warning

The stop valves are closed

Excessive refrigerant charge

Open the gas and liquid stop valves

Recalculate the additional refrigerant
charge and recover any excessive
refrigerant with a refrigerant recovery
machine

High pressure sensor ≥3.55 MPa (35.5 bar)

3

Warning

Inverter compressor motor lock

Position signal error

4

Warning

The stop valves are closed

Incorrect wiring

Open the gas and liquid stop valves

Ensure correct

Phase order

Wiring

Outdoor unit fan motor
malfunction

Irregular revolution of 1 fan motor

4

Caution

Fan motor malfunction:

M1F - A2P (X106A)

M2F - A2P (X107A)

Check actuator, or connection on PCB

Irregular revolution of 2 fan motors

4

Warning

Electronic expansion valve
abnormality

No continuity of electronic expansion valve
coil

0

Warning

Electronic expansion valve malfunction:
Y1E - A1P (X21A)

Check actuator, or connection on PCB

Abnormal discharge pipe
temperature

Discharge pipe temperature >150°C

0

Warning

Refrigerant shortage

Defective discharge thermistor or
outdoor unit PCB

Clogging of expansion valve for
injection

Charge additional refrigerant

Replace defective component

Repair clogging

Discharge pipe temperature >120°C
continuously for 70 seconds or more

Discharge pipe temperature >125°C
continuously for 30 seconds or more

Discharge pipe temperature >130°C

14

Warning

Discharge pipe temperature >110°C AND
Y1E ≥450 pls, continuously for 60 seconds

1

Caution

3

Warning

Wet operation from refrigeration
suction pipe

Suction superheat <5 K AND discharge
superheat <15 K AND discharge temperature
<60°C, continuously for 10 minutes

0

Caution

Excessive frost formation on indoor
side

Wrong selection of expansion valves

Adjust defrost cycle

Select the correct type of expansion
valve

In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours

0

Warning

Wet operation from injection pipe

Suction superheat ≥5 K AND discharge
superheat <15 K AND discharge temperature
<60°C, continuously for 90 minutes

0

Caution

Defective expansion valve, suction pipe
thermistor, or subcool heat exchanger
outlet thermistor

Refrigerant overcharge

Replace defective component

Adjust refrigerant charge

In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours

0

Warning

Содержание LRMEQ3BY1

Страница 1: ...Installer and user reference guide Air cooled refrigeration condensing unit English Installer and user reference guide Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1 LRLEQ3BY1 LRLEQ4BY1...

Страница 2: ...ervice port 16 6 4 6 To remove the pinched pipes 17 6 4 7 Guidelines when installing a sight glass 18 6 4 8 Guidelines when installing a dryer 18 6 4 9 To connect the refrigerant piping to the outdoor...

Страница 3: ...XPLOSION Indicates a situation that could result in explosion WARNING Indicates a situation that could result in death or serious injury WARNING FLAMMABLE MATERIAL CAUTION Indicates a situation that c...

Страница 4: ...unit Do NOT sit climb or stand on the unit NOTICE Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress In accordance with the applicable legislation it...

Страница 5: ...ide down Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when paus...

Страница 6: ...utside pressure being exerted on the terminal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will damage the head and make proper tightening im...

Страница 7: ...s of the unit Carry the unit slowly as shown Forklift As long as the unit remains on its pallet you can also use a forklift 3 2 3 To remove the accessories from the outdoor unit 1 Remove the service c...

Страница 8: ...ed at the following conditions ambient temperature 32 C evaporating temperature 35 C superheat 10 K 4 4 System layout c b d a a Outdoor unit ZEAS condensing unit b Refrigerant piping c Indoor unit Blo...

Страница 9: ...410A and the same oil FVC68D as the new one you must clean the heat exchanger tubes to remove any residue If the old condensing unit did NOT use the same refrigerant R410A as the new one make sure the...

Страница 10: ...t Where the voltage fluctuates a lot In vehicles or vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds This is to p...

Страница 11: ...Amount of refrigerant in a single unit system amount of refrigerant with which the system is charged before leaving the factory B Additional charging amount amount of refrigerant added locally C Total...

Страница 12: ...8 Annealed O 0 99 mm 19 1 mm 3 4 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thickness mig...

Страница 13: ...ndoor Example H Limit 20 m Outdoor lower than indoor 10 m Maximum height difference indoor indoor 5 m 5 3 7 To select the expansion valve This unit has a larger subcooling ratio for the liquid refrige...

Страница 14: ...bes what you have to do and know on site to install the system Typical workflow Installation typically consists of the following stages Mounting the outdoor unit Mounting the indoor units Connecting t...

Страница 15: ...can tilt the unit take following measure 1 Prepare 2 cables as indicated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cabl...

Страница 16: ...y affects valves and compressors in the refrigerating system and prevents proper operation Set the nitrogen pressure to 20 kPa 0 2 bar just enough so it can be felt on the skin with a pressure reducin...

Страница 17: ...le the service port Always use a charge hose equipped with a valve depressor pin since the service port is a Schrader type valve After handling the service port make sure to tighten the service port c...

Страница 18: ...lass before the dryer as near to the outdoor unit as possible Install horizontally a b a Sight glass b Dryer When brazing Follow the brazing instructions in the sight glass manual 6 4 8 Guidelines whe...

Страница 19: ...the required length e1 This is necessary because the size of the gas stop valve is 15 9 while the piping between outdoor unit and first refrigerant branch kit is 19 1 Possibility 1 To the front e1 e c...

Страница 20: ...il all moisture has been removed All piping inside the unit has been factory tested for leaks Only field installed refrigerant piping needs to be checked Therefore make sure that all the outdoor unit...

Страница 21: ...ice port of the liquid stop valve or first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 6 7 4 To charge refrigerant on p...

Страница 22: ...ils are used 0 6 kg Metric piping When using metric piping replace the weight factors in the formula by the ones from the following table Inch piping Metric piping Piping Weight factor Piping Weight f...

Страница 23: ...t evaporating temperature with settings 2 0 and 2 1 see 7 2 8 Mode 2 Field settings on page 30 18 Turn on the power of the indoor units 19 Turn on the operation switch Result The unit will start opera...

Страница 24: ...al refrigerant charge in kg 1000 2 Fix the label on the inside of the outdoor unit near the gas and liquid stop valves 6 8 Connecting the electrical wiring 6 8 1 About connecting the electrical wiring...

Страница 25: ...ther means for disconnection having a contact separation in all poles providing full disconnection under overvoltage category III condition MUST be installed in the fixed wiring WARNING ONLY use coppe...

Страница 26: ...size Tightening torque N m X1M power supply wiring power supply shielded ground M5 2 2 2 7 X2M remote operation switch low noise switch and transmission output M3 5 0 8 0 97 X3M output signals M4 2 3...

Страница 27: ...d before the earth wire is in case the power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break dow...

Страница 28: ...the hydro module To configure the condensing unit you must give input to the outdoor unit s main PCB A1P This involves the following field setting components Push buttons to give input to the PCB A di...

Страница 29: ...tion when shipped from factory 10 12 min b c a a Power ON b Default situation c LED indication when there is a malfunction If the default situation is not displayed after 10 12 minutes check the malfu...

Страница 30: ...ure With this setting the target evaporating temperature can be set in increments of 5 K default 10 C 35 C 20 C 45 C 15 C 40 C 5 C 30 C 0 C 25 C 5 C 20 C 2 1 Te fine tuning of evaporating temperature...

Страница 31: ...the indoor units When performing the test operation NOT only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangero...

Страница 32: ...describes the test operation of the complete system 8 4 2 To perform a test run 7 LEDs display 1 Make sure all field settings you want are set see 7 2 Making field settings on page 28 2 Turn ON the p...

Страница 33: ...a tester and confirm that the voltage of the capacitor in the main circuit is less than 50 V DC C C A1P A2P 3 To prevent damaging the PCB touch a non coated metal part to eliminate static electricity...

Страница 34: ...rigerant recovery machine High pressure sensor 3 55 MPa 35 5 bar 3 Warning Inverter compressor motor lock Position signal error 4 Warning The stop valves are closed Incorrect wiring Open the gas and l...

Страница 35: ...failure Open circuit or shortcircuit 0 Caution Faulty connection of sensor Defective sensor Connect the sensor properly Replace defective component Low pressure sensor failure Open circuit or shortcir...

Страница 36: ...1000 500 D 500 D E 1000 1000 500 B D 100 500 B D E HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU 200 1700 1000 500 HU a b...

Страница 37: ...2 A1 A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the...

Страница 38: ...Service port e Check valve f Maintenance stop valve g Liquid receiver h Heat exchanger i Oil separator j Distributor k Double tube heat exchanger l Propeller fan m Sight glass n Capillary tube M1C Co...

Страница 39: ...se the contact Legend for wiring diagram LRMEQ3 4 A1P Printed circuit board main A2P Printed circuit board inverter BS A1P Push buttons MODE SET RETURN TEST RESET C A2P Capacitor DS1 A1P DIP switch E...

Страница 40: ...protect the compressor 16 Operation 16 1 Operation range Use the system in the following temperature ranges for safe and effective operation LRMEQ LRLEQ Outdoor temperature 20 43 C DB Evaporating temp...

Страница 41: ...information When asking your dealer for an intervention always state The complete model name of the unit The manufacturing number stated on the nameplate of the unit The installation date The symptoms...

Страница 42: ...unit does not stop immediately when operation is stopped This is to prevent components from being damaged The unit will stop in a little while 19 1 3 Symptom Noise Outdoor unit A continuous low hissi...

Страница 43: ...th the product and that need to be installed according to the instructions in the accompanying documentation Optional equipment Equipment made or approved by Daikin that can be combined with the produ...

Страница 44: ...4P500362 1A 2018 09 Copyright 2016 Daikin...

Отзывы: