11 Troubleshooting
Installer and user reference guide
34
LRMEQ+4BY1
Air-cooled refrigeration condensing unit
4P500362-1A – 2018.09
DANGER: RISK OF ELECTROCUTION
WARNING
Prevent hazards due to inadvertent resetting of the thermal
cut-out: power to this appliance MUST NOT be supplied
through an external switching device, such as a timer, or
connected to a circuit that is regularly turned ON and OFF
by the utility.
DANGER: RISK OF BURNING
11.3
Solving problems based on error
codes
INFORMATION
When a malfunction occurs, X3M outputs a caution (C/C1)
or warning (C/W1) signal, and the H2P LED on the main
PCB lights up.
You can display the error codes of the 3 latest malfunctions by using
the push buttons and 7‑LEDs display (see
). Error codes consist of 2 characters
(example: E3).
After solving the problem, reset the malfunction by turning OFF and
ON the operation switch, and retry operation.
11.3.1
To display the error codes of the latest
malfunctions
#
Action
Display
1
Start from the default
situation.
2
Select mode 1.
BS1
[1×]
#
Action
Display
3
Select a malfunction.
("X×" depends on the
setting that you want
to select.)
BS2
[X×]
Possible malfunctions:
[1‑14] Latest malfunction:
[1‑15] 2nd last malfunction:
[1‑16] 3rd last malfunction:
4
Display the
first
character
of the error
code.
BS3
[1×]
Possible characters:
E:
H:
F:
J:
L:
P:
U:
5
Display the
second
character
of the error
code.
BS2
[1×]
Possible characters:
1:
2:
3:
4:
5:
6:
7:
8:
9:
A:
C:
6
Quit mode 1.
BS1
[1×]
11.3.2
Error codes: Overview
Code
Description
Criteria
Times of
retry
Output signal
Cause
Solution
Abnormally high pressure level
High pressure switch ≥4.0 MPa (40 bar)
0
Warning
▪
The stop valves are closed
▪
Excessive refrigerant charge
▪
Open the gas and liquid stop valves
▪
Recalculate the additional refrigerant
charge and recover any excessive
refrigerant with a refrigerant recovery
machine
High pressure sensor ≥3.55 MPa (35.5 bar)
3
Warning
Inverter compressor motor lock
Position signal error
4
Warning
▪
The stop valves are closed
▪
Incorrect wiring
▪
Open the gas and liquid stop valves
▪
Ensure correct
▪
Phase order
▪
Wiring
Outdoor unit fan motor
malfunction
Irregular revolution of 1 fan motor
4
Caution
Fan motor malfunction:
▪
M1F - A2P (X106A)
▪
M2F - A2P (X107A)
Check actuator, or connection on PCB
Irregular revolution of 2 fan motors
4
Warning
Electronic expansion valve
abnormality
No continuity of electronic expansion valve
coil
0
Warning
Electronic expansion valve malfunction:
Y1E - A1P (X21A)
Check actuator, or connection on PCB
Abnormal discharge pipe
temperature
Discharge pipe temperature >150°C
0
Warning
▪
Refrigerant shortage
▪
Defective discharge thermistor or
outdoor unit PCB
▪
Clogging of expansion valve for
injection
▪
Charge additional refrigerant
▪
Replace defective component
▪
Repair clogging
▪
Discharge pipe temperature >120°C
continuously for 70 seconds or more
▪
Discharge pipe temperature >125°C
continuously for 30 seconds or more
▪
Discharge pipe temperature >130°C
14
Warning
Discharge pipe temperature >110°C AND
Y1E ≥450 pls, continuously for 60 seconds
1
Caution
3
Warning
Wet operation from refrigeration
suction pipe
Suction superheat <5 K AND discharge
superheat <15 K AND discharge temperature
<60°C, continuously for 10 minutes
0
Caution
▪
Excessive frost formation on indoor
side
▪
Wrong selection of expansion valves
▪
Adjust defrost cycle
▪
Select the correct type of expansion
valve
In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours
0
Warning
Wet operation from injection pipe
Suction superheat ≥5 K AND discharge
superheat <15 K AND discharge temperature
<60°C, continuously for 90 minutes
0
Caution
▪
Defective expansion valve, suction pipe
thermistor, or subcool heat exchanger
outlet thermistor
▪
Refrigerant overcharge
▪
Replace defective component
▪
Adjust refrigerant charge
In addition to above conditions (for caution):
discharge superheat <15 K for 6 hours
0
Warning