SiENBE28-901
Troubleshooting
Air Cooled Refrigeration Condensing Unit
105
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Cut the power supply off.
Is the fan motor
connector (X2A)
properly connected
to the fan inverter
PCB?
YES
NO
Check the connector
of the fan motor (
∗
1).
Check if the resistance of
the fan motor lead wire
between Vcc and UVW and
between GND and UVW
are balanced.
YES
NO
Ensure correct connection.
Replace the fan motor.
Replace the inverter PCB.
z
For fan motor 1: replace the inverter
PCB (A4P).
z
For fan motor 2: replace the inverter
PCB (A8P).
∗
1. Check procedure for fan motor connector
(1) Power OFF the fan motor.
(2) Remove the connector (X2A) on the PCB to measure
the following resistance value.
Judgement criteria: resistance value between each
phase is within ±20%
Connector for
signal wires (X2A)
X2A
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc
W
V
U
Measure the
resistance
between Vcc-
UVW and
GND-UVW.