0-UC 13-FEB 18-2
Page 13
3.2
Capacity Table
(a)
Medium Temperature
Refrigerant
R404A
Refrigerant
R134a
Model
Te
-10
-8
-5
0
5
Model
Te
-10
-8
-5
0
5
LFMNS0150AXV1
1.48
1.50
1.54
1.66
1.79
LFMNS0150AXV1
1.35
1.37
1.4
1.51
1.63
LFMNS0400AXV1
3.85
3.90
4.01
4.3
4.63
LFMNS0400AXV1
3.51
3.55
3.65
3.91
4.21
LFMNS0600AXV1
5.83
5.90
6.07
6.58
7.05
LFMNS0600AXV1
5.3
5.37
5.52
5.98
6.41
LFMNS0800AXV1
7.95
8.05
8.28
8.91
9.37
LFMNS0800AXV1
7.24
7.33
7.54
8.1
8.53
LFMNS0980AXV1
9.67
9.80
10.07 10.71 11.16
LFMNS0980AXV1
8.8
8.92
9.17
9.75
10.16
LFMNS1400AXV1
13.94
14.20
14.52 15.28 15.76
LFMNS1400AXV1
12.68
12.92
13.21 13.91
14.34
*DT1=8K
DT1=Air inlet temperature (Ta)- Evaporating temperature at the outlet(Te)
TD CORRECTION FACTOR
Capacity at different TD can be calculated using the correction factor given in below table:
TD(K)
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
Correction
Factor
0.56
0.63
0.69
0.75
0.81
0.88
0.94 1.00
1.06
1.13
1.19
1.25
(b) Low Temperature
Refrigerant
R404A
Model Te
-40
-35
-30
-25
-20
LFLHS0150AXV1
0.81
1.04
1.27
1.50
1.73
LFLHS0200AXV1
1.49
1.66
1.83
2.00
2.17
LFLHS0320AXV1
2.21
2.54
2.87
3.20
3.53
LFLHS0400AXV1
2.74
3.16
3.58
4.00
4.42
LFLHS0480AXV1
3.27
3.78
4.29
4.80
5.31
LFLHS0600AXV1
4.05
4.70
5.35
6.00
6.65
*DT1=7K
DT1=Air inlet temperature (Ta)- Evaporating temperature at the outlet(Te)
TD CORRECTION FACTOR
TD(K)
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
Correction
Factor
0.64
0.71
0.79
0.86
0.93
1.00
1.07
1.14
1.21
1.29
1.36