English 5

 

Since the connector of the thermistor for detection of inlet air temperature 

differs depending on the indoor unit type, make sure to check the indoor unit 

wiring diagram and follow it correctly.

 

Lay and clamp the extension cable inside the indoor unit switch box just 

like the low voltage line (cord for remote controller). 

And do not pass where the extension cable inside the indoor unit switch 

box may be affected by the power line (cord for the indoor unit and the other 

electric line).

Procedure

1)  When wiring to the indoor unit PCB, remove the existing thermistor (for 

detection of inlet air temperature) and then connect the extension cable.

When doing this work, make sure to check the symbol of connecting 

address on the PCB whether it is correct or not referring to the wiring 

diagram.

For SkyAir VRV

1

a

b

c

d

b

e

f

2

X16A

a  Screwed terminal connection

b  Extension cable

c  Connector connection

d  Indoor unit

e  Indoor unit printed circuit board (PCB)

f  Existing thermistor or humidity sensor

1. Remove

2. Connect

Содержание KRCS01-7B

Страница 1: ...Remote sensor KRCS01 7B Installation Manual 4P564107 1...

Страница 2: ......

Страница 3: ...is drawing Mounting screw M4X16 Shape Quantity 1x 1x 2x 1x 2x Mounting Selection of mounting location The thermistor for temperature detection is incorporate into the remote sensor Select the mounting...

Страница 4: ...wall a b c d e f g a Mounting screw b Thermal insulation material c Knockout hole for cable d Sensor box e Air hole f Released paper g Sensor box cover 2 M4 32 42 Break open the knockout hole in the s...

Страница 5: ...ded wiring a b c d e f g h i j k l a Sensor box cover b Mounting screw c Sensor box d Metal plate for single unit without hole field supplied e Mounting frame which matches with the switch box field s...

Страница 6: ...that the connector side may not be cut 45 For M3 Round crimp terminal Wiring method Connect the extension cable connector side to the indoor unit PCB printed circuit board For connection to the indoo...

Страница 7: ...y be affected by the power line cord for the indoor unit and the other electric line Procedure 1 When wiring to the indoor unit PCB remove the existing thermistor for detection of inlet air temperatur...

Страница 8: ...etween the high voltage wiring and the low voltage wiring to avoid error of sensor Provide protection of the existing cable for thermistor without affecting other components 3 Fit the sensor box cover...

Страница 9: ......

Страница 10: ...4P564107 1 2018 12...

Отзывы: