Daikin IOM 1062 Скачать руководство пользователя страница 12

12

 

Direct Drive Fluid Coolers 

IOM 1062 

Table 7, Model 005 through 021, Physical Data 

Fan Data 

Model 

Fan 

Configuration 

Diameter of 

Fans 

Approx. 

Net 

Weight, lb. 

Approx. 

Shipping 

Weight, lb. 

Approx 

Operating 

Weight, lb. 

005 

1x1 

24 

180 

325 

240 

008 

1x1 

26 

260 

380 

330 

010 

1x2 

24 

450 

600 

537 

012 

1x2 

26 

470 

620 

557 

014 

1x2 

26 

510 

650 

615 

016 

1x2 

26 

530 

680 

635 

021 

1x3 

26 

550 

725 

698 

Note; Net weight is dry unit only. 

Table 8, Model 023 through 212, Physical Data 

Fan Data 

Model 

Fan 

Configuration 

Number of 

Fans 

CFM 

Operating 

Charge, gal. 

Approx. 

Net 

Weight, lb. 

Approx. 

Shipping 

Weight, lb. 

Approx. 

Operating 

Weight, lb. 

AFS Single-Row of Fans 

023 

1x2 

23,000 

6.7 

730 

800 

788 

027 

1x2 

23,200 

9.2 

790 

840 

870 

031 

1x2 

21,900 

9.2 

790 

860 

870 

035 

1x2 

20,700 

11.8 

889 

950 

992 

041 

1x3 

34,800 

13.0 

1190 

1280 

1303 

045 

1x3 

32,900 

13.0 

1210 

1300 

1323 

049 

1x3 

31,800 

16.7 

1240 

1330 

1385 

053 

1x4 

46,400 

16.7 

1580 

1690 

1725 

061 

1x4 

43,900 

16.7 

1620 

1730 

1765 

065 

1x4 

42,400 

21.7 

1650 

1760 

1839 

071 

1x4 

41,500 

21.7 

1760 

1870 

1949 

075 

1x5 

54,900 

20.4 

2000 

2150 

2177 

079 

1x5 

54,800 

26.6 

2020 

2150 

2251 

089 

1x5 

51,800 

26.6 

2200 

2390 

2431 

097 

1x6 

65,800 

31.6 

2390 

2610 

2665 

107 

1x6 

62,200 

31.6 

2630 

2850 

2905 

AFD Double Row of Fans 

046 

2x2 

46,000 

13.5 

1540 

1730 

1657 

054 

2x2 

46,400 

18.5 

1580 

1770 

1741 

060 

2x2 

43,900 

18.5 

1620 

1820 

1781 

066 

2x2 

42,400 

23.5 

1650 

1840 

1854 

070 

2x2 

41,500 

23.5 

1760 

1950 

1964 

080 

2x3 

69,700 

25.9 

2360 

2570 

2585 

086 

2x3 

67,000 

25.9 

2380 

2620 

2605 

090 

2x3 

65,800 

25.9 

2420 

2630 

2645 

098 

2x3 

63,600 

33.4 

2480 

2690 

2771 

106 

2x4 

92,900 

33.3 

3150 

3360 

3440 

120 

2x4 

87,800 

33.3 

3230 

3420 

3520 

132 

2x4 

84,800 

43.3 

3300 

3470 

3677 

140 

2x4 

83,000 

43.3 

3510 

3730 

3887 

152 

2x5 

10 

190,700 

40.7 

4040 

4290 

4394 

162 

2x5 

10 

109,700 

53.1 

3990 

4270 

4452 

168 

2x5 

10 

106,000 

53.1 

4130 

4450 

4592 

178 

2x5 

10 

103,700 

53.1 

4390 

4680 

4852 

194 

2x6 

12 

131,600 

63.1 

4790 

5150 

5339 

202 

2x6 

12 

127,200 

63.1 

4960 

5330 

5509 

212 

2x6 

12 

124,400 

63.1 

5270 

5670 

5819 

NOTES: 

1.

All fans are 30 inches in diameter.

2.

Net weight is unit only.

3.

Operating weight based on 50% ethylene glycol at 130

°

F.

Содержание IOM 1062

Страница 1: ...on Operation and Maintenance Manual IOM 1062 Group Chiller Part Number 331375001 Effective January 2010 Supersedes IOM AFSD 2 Direct Drive Fluid Coolers Type AFS 005 through AFS 107 Type AFD 046 throu...

Страница 2: ...col Sludge Prevention 10 Fluid Circulating Pump 10 Ambient Conditions 11 Physical Data 11 Dimensional Data 13 Electrical Data 15 Electrical Wiring 15 Wiring Diagrams 18 Start Up 19 Prestart 19 Filling...

Страница 3: ...IOM 1062 Direct Drive Fluid Coolers 3...

Страница 4: ...tion A Fan Cycling Thermostat with Control Transformer 120V E Control Transformer Only 120V Y None Rough Duty Options A Totally enclosed motors B Sealtite Wiring C PolyGuard fin coating with totally e...

Страница 5: ...ceed 2 5 All controls and equipment protection circuits properly connected per wiring diagram 6 Factory installed wiring must not be changed without written factory approval 7 Relief valves must meet...

Страница 6: ...ab with footings extending below the frost line Be certain concrete slabs are installed level and are properly supported to prevent settling Locate the unit far enough away from any wall or other obst...

Страница 7: ...l Walls or Obstructions Locate the unit to ensure that air can circulate freely and not be recirculated For proper air flow and access all sides of the unit must be at least the distance shown away fr...

Страница 8: ...m should provide maximum leak prevention Weld or sweat joints should be used where possible The fact that glycol solutions or other heat transfer fluids will leak where water will not must be taken in...

Страница 9: ...26 3 60 2 2 1 8 7 9 7 0 80 2 2 1 8 13 7 12 0 100 2 1 2 2 5 8 8 5 6 1 150 2 1 2 2 5 8 18 6 12 9 200 3 3 1 8 10 7 9 1 250 3 3 1 8 16 5 13 7 300 3 1 2 3 5 8 11 1 9 2 300 4 4 1 8 5 9 4 9 350 4 4 1 8 7 9 6...

Страница 10: ...o sludge formation in coils due to one or more of the following causes Reaction of the corrosion inhibitor with galvanized piping zinc Reaction of the glycol with chromate type water additives Reactio...

Страница 11: ...in older systems have non operating standby pumps of equal capacity to the operating unit We recommend parallel pumps in continuous operation because they provide practically the same type of standby...

Страница 12: ...00 21 7 1650 1760 1839 071 1x4 4 41 500 21 7 1760 1870 1949 075 1x5 5 54 900 20 4 2000 2150 2177 079 1x5 5 54 800 26 6 2020 2150 2251 089 1x5 5 51 800 26 6 2200 2390 2431 097 1x6 6 65 800 31 6 2390 26...

Страница 13: ...hes AFS Model Number of Fans A B 005 1 39 30 008 1 49 40 010 2 69 60 012 2 69 60 014 2 89 80 016 2 89 80 021 3 129 120 NOTES 1 Inlet is the top connection outlet the bottom See Table 4 on page 11 for...

Страница 14: ...r 42 inches 2 Inlet is the top connection outlet the bottom See Physical Data beginning on page 11 for connection sizes 3 The electrical box is on the same end as the fluid connections with knockouts...

Страница 15: ...ead of starters requiring thermal protectors eliminating the problem of furnishing the proper heating elements All fluid coolers are furnished with either single phase or three phase fan motors which...

Страница 16: ...071 1x4 4 35 710 28 0 29 8 30 14 0 14 9 15 11 2 12 0 15 075 1x5 5 46 610 35 0 36 8 40 17 5 18 4 20 14 0 14 8 15 079 1x5 5 46 200 35 0 36 8 40 17 5 18 4 20 14 0 14 8 15 089 1x5 5 44 580 35 0 36 8 40 17...

Страница 17: ...2 0 12 5 15 107 1x6 6 28 8 30 0 30 14 4 15 0 15 12 0 12 5 15 AFD Double Row of Fans 046 2x2 4 19 2 20 4 25 9 6 10 2 15 8 0 8 5 10 054 2x2 4 19 2 20 4 25 9 6 10 2 15 8 0 8 5 10 060 2x2 4 19 2 20 4 25 9...

Страница 18: ...18 Direct Drive Fluid Coolers IOM 1062 Wiring Diagrams Figure 6 Typical Wiring for AFS Models NOTE Unit specific wiring diagrams are shipped with the unit...

Страница 19: ...mped into the system Temperature Control General Some method of controlling the fluid temperature is required The standard temperature control consists of fan contactors arranged for field connection...

Страница 20: ...t mode is set to Cut out the setpoint is the temperature at which the N O contacts open Refer to Figure 9 and Figure 10 Differential dIF establishes the difference in temperature between Cut in and Cu...

Страница 21: ...per at P4 establishes whether Setpoint is the Cut in temperature or Cut out temperature Keypad Lock Removing or installing the jumper at P5 establishes whether the keypad is locked or unlocked Locking...

Страница 22: ...gs Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the output relay is energized and the N O contacts are closed Cooling Heating and Setpoint Modes Jumpers...

Страница 23: ...energizes and LED indicator illuminates when the temperature drops to Setpoint minus the differential value When the temperature rises to Setpoint the output relay and LED indicator de energize Figure...

Страница 24: ...on a jumper in the Removed position place the jumper on only one pin Saving the jumper in case it is required in the future See Figure 11 Set the jumpers as follows using Figure 11 and Figure 12 as gu...

Страница 25: ...9 control is set at the factory to display in Fahrenheit temperature units To convert to Celsius units press the Up and Down buttons simultaneously Press them again to return to Fahrenheit units Note...

Страница 26: ...n mode and setpoint plus differential is greater than 212 F 100 C the control switches on at setpoint and off when the temperature exceeds 212 F 100 C Cooling Cut out If the control is operating in Co...

Страница 27: ...sly programmed value for that function Checkout Before applying power make sure installation and wiring connections are according to job specifications After necessary adjustments and electrical conne...

Страница 28: ...thermometer c Disconnect the sensor from the control d Using an ohmmeter measure the resistance across the two sensor leads while the sensor is at the temperature taken in step b e Consult Figure 14...

Страница 29: ...gized at Output Relay De energized at Cooling Setpoint plus differential Setpoint Cut out Heating Setpoint minus differential Setpoint Cooling Setpoint Setpoint minus differential Cut in Heating Setpo...

Страница 30: ...he unit coil will require periodic cleaning based on operation and atmosphere conditions Clean the unit using a brush or commercially available coil cleaners and water Take care not to deform the fin...

Страница 31: ......

Страница 32: ...ining or call 540 248 9646 and ask for the Training Department Warranty All Daikin equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult yo...

Отзывы: