5. BACnet® Server Gateway Points List
DCM014A51
Quick User Guide
7
Instance
No.
Object_Name
Type
Inactive
Active
Remarks
Text-1
Text-2
Text-3
Text-4
Text-5 Text-6
Text-7 Text-8
16
Fan Speed
MV
Low
Reserved
Medium Reserved High Reserved Reserved Auto
17
Airflow Direction
MV
P0
P1
P2
P3
P4
Reserved Reserved
P7
18
Timed Override
Operation
BV
Disable
Enable
19
Current Unit
Operation
MI
Off
Normal
Override Setback
20
Remote Controller
Prohibit
MV
Permit
Prohibit
Stop Only
21
Remote Controller
Prohibit
(Operation Mode)
BV
Permit
Prohibit
22
Remote Controller
Prohibit
(Setpoint)
BV
Permit
Prohibit
23
Filter Sign Status
BI
Normal
Alarm
24
Filter Sign Reset
BV
Reset
Alarm
25
Indoor Fan Status
BI
Off
On
26
Communication
Status
BI
Normal
Alarm
27
Thermo-on Status
BI
Off
On
28
Compressor Status
MI
Off
On
Defrost/
Hot Start
29
Aux Heater Status
BI
Off
On
30
Forced Thermo-off
BV
Disable
Enable
31
Indoor Unit
Changeover Option
BI
Not
Available
Available
*1: The unit of temperature (Celsius or Fahrenheit) follows the iTM locale (regional settings).
*2: The number of valid digits for each object is shown in the table below. If a value entered from BMS has a higher precision than the
number of significant digits of an object, the digits after the significant digits are rounded.
(For example, when OccCoolingSetpoint is "75.55" in degrees Fahrenheit, round it to "76".)
Regarding values in commands sent from the BMS, the iTM rounds them off to the number of the significant digits.
(For example, if the value in a command for OccCoolingSetpoint is "75.55" in degrees Fahrenheit, it is rounded to "76".)