IM 830-6
16 www.DaikinApplied.com
Figure 30: Suggested method for fastening louver (without flange
inside wall opening.
Wall Opening
Louver
(Bird Screen Not Shown)
Angle Iron
(by others)
Room Side
Exterior
Figure 31: Louver Installation with Flange
Caulk
(Top and 2 Sides)
Louvers
Drain Holes
(Do Not Block)
Flange (4 Sides)
1" Minimum
Lintels (By Others)
Bird Screen
Sealed Cement Mortar
Pitched Away from Unit
Toward Louver
Vertical or Horizontal Blade Wall Intake Louver (Vertical
Blade Shown)
Figure 32: Louver Installation Recessed without Flange
Drain Holes
(Do Not Block
With Mortar
or Caulking
Materials
Bird Screen
Sealed Cement
Mortar Pitched
Away from Unit
Toward Louver
1" Minimum
Lintels (By Others)
Louvers
Vertical or Horizontal Blade Wall Intake Louver
(Horizontal Blade Shown)
Installing the VentiMatic
Shutter Assembly
The VentiMatic Shutter Assembly is mounted on an installed
wall louver. For larger units with 100% ventilation air dampers,
two VentiMatic Shutters may be mounted side by side on the
same louver. See
The size and appearance of the wall louvers and the
VentiMatic Shutter are identical, with or without optional grilles
used with the unit ventilator
When installing VentiMatic Shutter(s) on the wall louver, make
sure all moving parts are free to operate unobstructed and
placed level and plumb for proper operation. If optional steel
interior wall grille is furnished, install as shown in
Figure 33: Louver, VentiMatic Shutter, Interior Wall Grille Details,
Dimensions
C
)
As Directed By Architect
3⁄4" (19mm) Approx.
7"
(178mm)
Cement Mortar
Steel Interior Wall
Grille(Optional)
See Note 3 below
12
5
⁄
8
"
(314mm)
3⁄4" (19mm) Approx.
Bird
Screen
Do Not Block Drain Holes With Caulk or Mortar
Not Less
Than 9"
(229mm)
Cement Mortar
Notes:
1.
Horizontal blade wall louver shown. Vertical blade wall louver also
available with Ventimatic shutter.
2.
Optional exterior grille matches unit ventilator wall louver in mate-
rial and design. Mounted on wall louvers.
3.
Optional steel interior wall grille should be used to conceal the
interior wall opening whenever the Ventimatic shutter is not located
behind shelf cabinets or DraftStop enclosure. Hardware to mount
the interior wall grille is not included.
Wall Openings and Louvers
Be sure that the exterior wall openings and louvers, as
applicable, are ready and in accordance with the job plans.
Horizontal Ceiling Models AHF, AHV, AHR, and AHB are
typically installed in the ceiling in close proximity to an outside
wall containing a properly sized louver that is designed to let in
outside air while preventing water (such as rain) from getting
past the louver and into the unit itself. A weather-tight seal
keeps unwanted air and moisture from entering the occupied
space. See
, and
for
various louver details.
Содержание IM 830-6