www.DaikinApplied.com 25
IM 830-6
Chilled Water and Heating Coils
Figure 7: Chilled/Hot Water (2-pipe) Unit (Coils U[1], D[2],
E[3], F[4])
Figure 8: Chilled and Hot Water Unit (Cooling Coils V[5],
S[6], W[7] Y[8]; Heating Coils 65, 66, 67)
Notes:
1.
All coils have the same end supply and return connections.
2.
All water coil connections are
⅞
" I.D. (female) sweat and all steam
coils are 1
⅛
" (female) sweat connections. All coil connections
terminate 9" (229mm) from the end of the unit.
3.
Steam coils have a factory installed pressure equalizing valve and
a 24" (610mm) long pressure equalizing line which terminates in a
½
" M.P.T. fitting.
4.
Steam/hot water connections may be same end as cooling coil con-
nections, but they are recommended to be opposite end to facilitate
piping. (Must be opposite end when using MicroTech controls.)
5.
Condensate connection is same end as cooling coil connections,
but is field reversible. Drain can be sloped in field.
6.
Electric heating coil power connections are right end only. Junction
box has 1" (25mm) and 2" (51mm) (trade size) knockouts, 10
½
"
(267mm) from right end of the unit.
7.
All dimensions are approximated.
Figure 9: Chilled Water & Steam Unit (Cooling Coils V[5],
S[6]; Heating Coils 68, 69)
Figure 10: Chilled Water (1st Position) & Electric Heating
(Cooling Coils V[5], S[6], W[7]; Heating Coil 12, 13)
Note:
Electric heat, right hand only. Chilled water left hand only
Table 7: Heat / Cool Coil Position / Combinations In Air Stream
First Position in Air Stream
Second Position in Air Stream
U, D, E,F, 1, 2, 3, 4
00
65, 66, 67, 68, 69
V, S, 5, 6
65, 66
W, 7
68, 69
G, 9
V, S W, 5, 6, 7
12
65, 66, 67
G, 9
Heating Coils
Cooling Coils
65 = 1-row Hot Water Coil
U or 1 = 2-row CW/HW 2-pipe
66 = 2-row Hot Water Coil
D or 2 = 3-row CW/HW 2-pipe
67 = 3-row Hot Water Coil
E or 3 = 4-row CW/HW 2-pipe
68 = Low Capacity Steam Coil F or 4 = 5-row CW/HW 2-pipe
69 = High Capacity Steam Coil V or 5 = 2-row CW Coil
12 = Low Electric Heat Coil
S or 6 = 3-row CW Coil
00 = None
W or 7 = 4-row CW Coil
G or 9 = Direct Expansion Coil