Inspecting the Outdoor Unit
SiAUY361411EA
191
Parts Inspection
1.25 Inspecting the Solenoid Valves
1. While the unit is running, turn ON each solenoid valve either directly or via the actuator
check function, and check the output voltage and operating noise at the output connector
(shown in the figure above) of the circuit board.
2. If the output voltage is significantly different, check the continuity between the solenoid coil
and circuit board harness as well as the coil resistance with the power OFF.
3. While the unit is running, turn OFF each solenoid valve, and check if there is a temperature
difference between the upstream and downstream of the solenoid valve. If there is no
temperature difference, chances are that the solenoid valve has been opened by foreign
matter caught in it.
4. While the unit is running, check if the refrigerant flowing noise changes as expected when
each solenoid valve turns from ON to OFF.
Output voltage
Inspecting the solenoid valves
Inspect each solenoid valve coil by measuring the resistance between its connectors.
The measured value is 1.2 k
Ω
for items marked with
∗
.
Parts to inspect
Measuring points
With actuator check
ON or solenoid valve
ON while running
Solenoid valve 31
Between power supply circuit board's CN112-1 and -3 Actuator CH35 200 V
Solenoid valve 1
Between power supply circuit board's CN113-1 and -3 Actuator CH13 200 V
Solenoid valve 2
Between power supply circuit board's CN114-1 and -3
Actuator CH14 200 V
Solenoid valve 37
Actuator CH41 200 V
Solenoid valve 3
Between power supply circuit board's CN115-1 and -3 Actuator CH15 200 V
Solenoid valve 12
Between power supply circuit board's CN116-1 and -3
Actuator CH69 200 V
Solenoid valve 3E
∗
Actuator CH76 200 V
Solenoid valve 6
Between power supply circuit board's CN124-1 and -3 Actuator CH61 200 V
Solenoid valve 9
Between power supply circuit board's CN125-1 and -3 Actuator CH64 200 V
Solenoid valve 10
∗
Between power supply circuit board's CN126-1 and -3 Actuator CH65 200 V
Solenoid valve 4
Between power supply circuit board's CN127-1 and -3 Actuator CH16 200 V
Solenoid valve 7
Between power supply circuit board's CN128-1 and -3 Actuator CH62 200 V
Solenoid valve 8
Between power supply circuit board's CN129-1 and -3
Actuator CH63 200 V
Solenoid valve 3F
∗
Actuator CH77 200 V
Solenoid valve 12
Between sub circuit board's CN303-1 and -3
Actuator CH43 200 V
Solenoid valve 13
Between sub circuit board's CN304-1 and -3
Actuator CH71 200 V
Solenoid valve 32
Between sub circuit board's CN305-1 and -3
Actuator CH36 200 V
Solenoid valve 3A
Between sub circuit board's CN306-1 and -3
Actuator CH72 200 V
Solenoid valve 3B
Between sub circuit board's CN307-1 and -3
Actuator CH73 200 V
Solenoid valve 3C
Between sub circuit board's CN308-1 and -3
Actuator CH74 200 V
Solenoid valve 3D
Between sub circuit board's CN309-1 and -3
Actuator CH75 200 V
Solenoid valve 3G
Between sub circuit board's CN310-1 and -3
Actuator CH78 200 V
Solenoid valve 3H
Between sub circuit board's CN311-1 and -3
Actuator CH79 200 V
Measuring points
Measured value
Between solenoid valve terminals
0.95 k
Ω
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...