Troubleshooting by Remote Controller
ESIE15-13B
122
Service Diagnosis
4.2
Error Codes and Description
Remote
Controller
Display
Contents of Error
Reference Page
Indoor Unit
A1
Indoor unit PCB abnormality
A3
Drain water level system abnormality
A6
Indoor unit fan motor abnormality
AJ
Capacity setting abnormality
C1
Transmission Error (between indoor unit PCB and adaptor PCB)
C4
Heat exchanger thermistor system abnormality
C5
Intermediate heat exchanger thermistor system abnormality
C9
Suction air thermistor system abnormality
CC
Humidity sensor system abnormality
CE
Malfunction of Motion Sensor / Floor Temperature Sensor
CJ
Remote controller thermistor abnormality
Outdoor
Unit
E1
Outdoor unit PCB abnormality
E3
High pressure abnormality (detected by the high pressure switch)
E4
Actuation of pressure sensor
E5
Compressor motor lock
E7
Outdoor unit fan motor abnormality
E9
Electronic expansion valve abnormality
F3
Discharge pipe temperature control
H3
High pressure switch system abnormality
H4
Abnormal low pressure sensor
H9
Outdoor air thermistor system abnormality
J3
Discharge pipe thermistor system abnormality
J5
Suction pipe thermistor system abnormality
J6
Heat exchanger thermistor system abnormality
J7
Intermediate heat exchanger thermistor system abnormality
J8
Liquid pipe thermistor system abnormality
L1
Outdoor unit PCB abnormality
L4
Radiation fin temperature rise
L5
Output overcurrent detection
L8
Electronic thermal (time lag)
L9
Stall prevention (time lag)
LC
Transmission system abnormality (between control and inverter PCB)
P1
Open phase or power supply voltage imbalance
PJ
Defective capacity setting
U0
Refrigerant shortage
U2
Power supply voltage abnormality
System
U4
Transmission error between indoor and outdoor unit
U5
Transmission error between remote controller and indoor unit
U8
Transmission error between MAIN remote controller and SUB remote controller
UA
Field setting switch abnormality
UC
Address duplication of centralized controller
UE
Transmission error between centralized controller and indoor unit
UF
Transmission error between indoor and outdoor unit / piping and wiring
mismatch / refrigerant shortage
Содержание GQI-Eco Series
Страница 2: ......
Страница 6: ...ESIE15 13B iv Table of Contents...
Страница 14: ...Introduction ESIE15 13B xii...
Страница 18: ...Outlook Outdoor Units ESIE15 13B 4 General Information 2 Outlook Outdoor Units...
Страница 22: ...Operating range ESIE15 13B 8 General Information...
Страница 108: ...Emergency Operation ESIE15 13B 94 Field Setting...