Summary of field settings
Mode
No.
(Note 1)
First
code
No.
Description of setting
Second code No. (Note 2)
01
02
03
04
10
(20)
0
Filter
contamination -
Heavy/Light
= Setting to
define time
between 2 filter
cleaning display
indications.
(When
contamination
is high, setting
can be changed
to half the time
in-between 2 filter
cleaning display
indications.)
Long
Life
Filter
Light
±2,500 hrs.
Heavy
±1,250 hrs.
—
—
2
Thermostat sensor
selection
Use both the
unit sensor
(or remote
sensor if
installed) AND
the remote
controller
sensor.
(See note 4+5)
Use unit
sensor only
(or remote
sensor if
installed).
(See note
4+5)
Use
remote
controller
sensor
only.
(See note
4+5)
—
3
“Time to clean filter”
displayed or not
displayed
Display
Do not
display
—
—
5
Information to
I-manager,
I-touch controller
Only unit
sensor
value (or
remote
sensor
value if
installed).
Sensor
value as set
by 10-2-0X
or 10-6-0X.
—
—
6
Thermostat sensor in
group control
Use unit
sensor only
(or remote
sensor if
installed).
(See note 5)
Use both the
unit sensor
(or remote
sensor if
installed) AND
the remote
controller
sensor. (See
note 3+4+5)
—
—
12
(22)
0
Output signal X1-
X2 of the optional
KRP1B PCB kit
Thermostat-on +
compressor run
—
Operation Malfunction
1
ON/OFF input from outside
(T1/T2 input) = Setting
when forced ON/OFF is to
be operated from outside.
Forced OFF
ON/OFF
operation
—
—
2
Thermostat
differential
changeover = Setting
when remote sensor
is used.
1.8°F
(1°C)
0.9°F
(0.5°C)
—
—
3
Fan setting during
thermostat OFF at
heating operation
LL
Set speed
—
—
4
Differential automatic
changeover
0°F
(0°C)
1.8°F
(1°C)
3.6°F
(2°C)
5.4°F
(3°C)
(See
note 6)
5
Auto-restart after
power failure
Disabled
Enabled
—
—
6
Fan setting during
thermostat OFF at
cooling operation
LL
Set speed
—
—
13
(23)
0
Setting for air outlet
velocity
This setting is to be
changed in function
of ceiling height.
≤8 to 3/4 ft.
(2.7 m or
less)
8-3/4 to 10
(2.7-3.0)
10 to
11-1/2
(3.0-
3.5)
—
1
Selection for air flow
direction
This setting is to
be changed when
blocking pad optional
kit is used.
4-way flow 3-way flow
2-way
flow
—
4
Airflow direction
range setting
This setting is to be
changed when range
of horizontal blade
movement needs to
be changed.
Upper
Medium
Lower —
Note 1:
Setting is carried out in the group mode, however, if the mode
number inside parentheses is selected, indoor units can also
be set individually.
Note 2:
Factory settings of the Second code No. are marked in grey
background.
Note 3:
If group control is selected and remote controller sensor is to
be used, then set 10-6-02 & 10-2-03.
Note 4:
If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at
the same time, then setting 10-2-01, 10-2-02 or 10-2-03 have
priority.
Note 5:
If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at
the same time, then setting for group connection, 10-6-01 has
priority and for individual connection, 10-2-01, 10-2-02 or
10-2-03 have priority.
Note 6:
More settings for Differential automatic change over
temperatures are:
Second code No.
05
7.2°F (4°C)
06
9.0°F (5°C)
07 10.8°F (6°C)
08 12.6°F (7°C)
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.