Troubleshooting
SiE 00-07
140
Troubleshooting R-407C PLUS Series
3.18
Outdoor Unit: Abnormal Discharge Pipe Temperature
Remote Controller
Display
F3
Supposed Causes
Abnormal discharge pipe temperature
Defect of discharge pipe thermistor (5K: R3T 8K, 10K: R3-1T, R3-2T)
Defect of outdoor unit PC board
Discharge pipe thermistor wrong connection
Liquid injection solenoid valve wrong connection
Troubleshooting
(VF044)
Discharge pipe
temperature is 135˚C
or higher.
Is there
a wrong connection of the
injection solenoid valves
Y3S, Y4S and Y5S?
Is there
a wrong
connection of the
discharge pipe thermistor?
R3-1(11)T (inverter side)
X16A R3-2(12)T (standard
side) X17A and R3-13T
(standard side)
X21A for 24~30
class.
Are
the characteristics
of the discharge pipe
thermistor normal?
(R3-1T, R3-2T or
R3-11T~13T) (For the
characteristics
table.)
Replace outdoor unit PC board A1P.
(or A3P for 24~30 class)
Connect correctly and turn on again.
Replace the discharge pipe thermistor.
NO
NO
NO
NO
Out of gas, compression defect, etc.
Defect of the refrigerant system.
YES
YES
YES
YES
Содержание FXYBP20K7V1
Страница 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Страница 11: ...Introduction SiE 00 07 x ...
Страница 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Страница 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Страница 90: ...SiE 00 07 Test Operation Test Operation R 407C PLUS Series 79 1 3 Outdoor Unit PC Board Ass y Outdoor Unit ...
Страница 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Страница 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...