• Indoor Unit • 4-way blow ceiling suspended unit • FXUQ-A
1
2
• VRV Systems • Indoor Unit
4
2
Specifications
Standard Accessories : Washer clamp;
Standard Accessories : Clamps;
Standard Accessories : Washer for hanger bracket;
Standard Accessories : Clamp metal;
Standard Accessories : Drain hose;
Standard Accessories : Declaration of conformity;
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;
Notes
(1) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(2) Maximum allowable voltage range variation between phases is 2%.
(3) MCA/MFA: MCA = 1.25 x FLA
(4) MFA
≤
4 x FLA
(5) Next lower standard fuse rating minimum 16A
(6) Select wire size based on the value of MCA
(7) Instead of a fuse, use a circuit breaker
2-2 Electrical Specifications
FXUQ71A
FXUQ100A
Power supply
Phase
1~
Frequency
Hz
50/60
Voltage
V
220-240/220-230
Voltage range
Min.
%
10
Max.
%
10
Current - 50Hz
Minimum circuit amps (MCA)
A
0.6
1.4
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Fan motor
A
0.5
1.1
Current - 60Hz
Minimum circuit amps (MCA)
A
0.6
1.4
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Fan motor
A
0.5
1.1