FXSQ-PAVE EDFMT391737

46

3P432203-4B

14. Installation Manual

CONTENTS

  1.  SAFETY PRECAUTIONS ..............................................1
  2.  BEFORE INSTALLATION ..............................................2
  3.  SELECTION OF INSTALLATION LOCATION ................4
  4.  PREPARATION BEFORE INSTALLATION ....................5
  5.  INSTALLATION OF INDOOR UNIT ...............................6
  6.  REFRIGERANT PIPING WORK ....................................7
  7.  DRAIN PIPING WORK ..................................................8
  8.  DUCT WORK ...............................................................11
  9.  ELECTRIC WIRING WORK .........................................11
 10.  FIELD SETTING ..........................................................15
 11.  TEST OPERATION ......................................................16
 12.  WEIGHT AND DIMENSION 

 

........................................16

1.  SAFETY PRECAUTIONS

Please read the these " SAFETY CONSIDERATIONS" 
carefully before installing air conditioning unit and be sure to 
install it correctly. After completing the installation, make sure 
that the unit operates properly during the start-up operation.
Please instruct the customer on how to operate the unit and  
keep it maintained.
Also, inform customers that they should store this installation 
manual along with the operation manual for future reference.

 

This product comes under the term “appliances not accessible 
to the general public”.
This is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

• 

This manual 

classifies

 the precautions into WARNINGS and 

CAUTIONS. 
Be sure to follow all the precautions below: They are all 
important for ensuring safety.

 

WARNING

  .............. Indicates a potentially 

hazardous situation which, 
if not avoided, could result in 
death or serious injury.

 

CAUTION

  ............... Indicates a potentially 

hazardous situation which, 
if not avoided, may result in 
minor or moderate injury. 
It may also be used to alert 
against unsafe practices.

• 

After the installation is completed, test the air conditioner 
and check if the air conditioner operates properly. Give the 
user adequate instructions concerning the use and cleaning 
of the indoor unit according to the Operation Manual. Ask the 
user to keep this manual and the Operation Manual together 
in a handy place for future reference.

 WARNING

• 

Ask your local dealer or 

qualified

 personnel to carry out 

installation work. 
Improper installation may result in water leakage, electric 
shocks or a 

fir

e.

• 

Perform installation work in accordance with this installation 
manual. 
Improper installation may result in water leakage, electric 
shocks or a 

fir

e.

• 

Consult your local dealer regarding what to do in case of 
refrigerant leakage. 
When the air conditioner is installed in a small room, it is 
necessary to take proper measures so that the amount of 

any leaked refrigerant does not exceed the concentration 
limit in the event of a leakage. 
Otherwise, this may lead to an accident due to oxygen 

deficienc

y.

• 

Be sure to use only the 

specified

 parts and accessories for 

installation work. 
Failure to use the 

specified

 parts may result in the air 

conditioner falling down, water leakage, electric shocks, a 

fir

e, etc.

• 

Install the air conditioner on a foundation that can withstand 
its mass. 

Insufficient

 strength may result in the air conditioner falling 

down and causing injury. 
In addition, it may lead to vibration of indoor units and cause 
unpleasant chattering noise.

• 

Carry out the 

specified

 installation work in consideration of 

strong winds, typhoons, or earthquakes. 
Improper installation may result in an accident such as air 
conditioner falling.

• 

Make certain that all electrical work is carried out by 

qualified 

personnel according to the applicable legis lation (Note 1) 
and this installation manual, using a separate circuit.  
In addition, even if the wiring is short, make sure to use a 
wiring that has 

sufficient

 length and never connect additional 

wiring to make the length 

sufficient.

 

Insufficient

 capacity of the power supply circuit or improper 

electrical construction may lead to electric shocks or a 

fir

e.

(Note 1)   applicable legislation means “All international, 

national and local directives, laws, regulations  
and/or codes which are relevant and applicable for 
a certain product or domain”.

• 

Earth the air conditioner. 
Do not connect the earth wiring to gas or water piping, 
lightning conductor or telephone earth wiring. 
Incomplete earthing may cause electric shocks or a 

fir

e.

• 

Be sure to install an earth leakage breaker. 
Failure to do so may cause electric shocks and a 

fir

e.

• 

Disconnect the power supply before touching the electric 
components. 
If you touch the live part, you may get electric shocks.

• 

Make sure that all wiring is secure, using the 

specified 

wirings and ensuring that external forces do not act on the 
terminal connections or wirings. 
Incomplete connection or 

fixing

 may cause an overheat or a 

fir

e.

FXSQ20P

A

VE

FXSQ25PAVE

FXSQ32PAVE

FXSQ40PAVE

FXSQ50PAVE

FXSQ63PAVE

FXSQ80PAVE

FXSQ100PAVE

FXSQ125PAVE

FXSQ140PAVE

VRV SYSTEM  

Air Conditioner

Installation manual

Содержание FXSQ-PAVE

Страница 1: ...FXSQ PAVE EDFMT391737 201709 Engineering Data 50 60 Hz...

Страница 2: ......

Страница 3: ...Safety Devices Setting 17 8 Capacity Tables 18 8 1 Cooling Capacity for Te Auto 18 8 2 Cooling Capacity for Te 6 C 18 8 3 Cooling Capacity for Te 9 C 19 8 4 Heating Capacity 19 9 Fan Performances 20 1...

Страница 4: ...5 40 50 62 5 80 100 125 140 FXSQ 20PAVE 25PAVE 32PAVE 40PAVE 50PAVE 63PAVE 80PAVE 100PAVE 125PAVE 140PAVE FXSQ for Thailand 20PAVS 25PAVS 32PAVS 40PAVS 50PAVS 63PAVS 80PAVS 100PAVS 125PAVS 140PAVS FXS...

Страница 5: ...expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operati...

Страница 6: ...ion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operation man...

Страница 7: ...xpansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Operatio...

Страница 8: ...c expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange Opera...

Страница 9: ...tronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing material Clamps Washers Screws Thermal insulation Hose band Air discharge flange Air suction flange...

Страница 10: ...FXSQ PAVE EDFMT391737 8 3 Dimensions FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 3D095725B Unit mm...

Страница 11: ...FXSQ PAVE EDFMT391737 9 FXSQ40PAVE 3D095726B Unit mm...

Страница 12: ...FXSQ PAVE EDFMT391737 10 FXSQ50PAVE 3D096164B Unit mm...

Страница 13: ...FXSQ PAVE EDFMT391737 11 FXSQ63PAVE FXSQ80PAVE 3D095426D Unit mm...

Страница 14: ...FXSQ PAVE EDFMT391737 12 FXSQ100PAVE FXSQ125PAVE 3D095427D Unit mm...

Страница 15: ...FXSQ PAVE EDFMT391737 13 FXSQ140PAVE 3D095727C Unit mm...

Страница 16: ...PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE 12...

Страница 17: ...FXSQ PAVE EDFMT391737 15 5 Wiring Diagrams FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 3D092752C...

Страница 18: ...FXSQ PAVE EDFMT391737 16 6 Electric Characteristics FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D105290...

Страница 19: ...V 6 3 A Drain pump thermal fuse C Model FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE Printed circuit board fuse 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A 250 V 3 15 A Printed circuit board fuse Fan drive...

Страница 20: ...length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 1...

Страница 21: ...8 TC Total capacity kW SHC Sensible heat capacity kW Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the sel...

Страница 22: ...FXSQ PAVE EDFMT391737 20 9 Fan Performances FXSQ20PAVE FXSQ25PAVE 3D095855A...

Страница 23: ...FXSQ PAVE EDFMT391737 21 FXSQ32PAVE 3D095856A...

Страница 24: ...FXSQ PAVE EDFMT391737 22 FXSQ40PAVE 3D095857A...

Страница 25: ...FXSQ PAVE EDFMT391737 23 FXSQ50PAVE 3D095858A...

Страница 26: ...FXSQ PAVE EDFMT391737 24 FXSQ63PAVE 3D095859A...

Страница 27: ...FXSQ PAVE EDFMT391737 25 FXSQ80PAVE 3D095860A...

Страница 28: ...FXSQ PAVE EDFMT391737 26 FXSQ100PAVE 3D095861A...

Страница 29: ...FXSQ PAVE EDFMT391737 27 FXSQ125PAVE 3D095862A...

Страница 30: ...FXSQ PAVE EDFMT391737 28 FXSQ140PAVE 3D095863A...

Страница 31: ...FXSQ PAVE EDFMT391737 29 10 Airflow Auto Adjustment Characteristics FXSQ20PAVE FXSQ25PAVE 3D095846A...

Страница 32: ...FXSQ PAVE EDFMT391737 30 FXSQ32PAVE 3D095847A...

Страница 33: ...FXSQ PAVE EDFMT391737 31 FXSQ40PAVE 3D095848A...

Страница 34: ...FXSQ PAVE EDFMT391737 32 FXSQ50PAVE 3D095849A...

Страница 35: ...FXSQ PAVE EDFMT391737 33 FXSQ63PAVE 3D095850A...

Страница 36: ...FXSQ PAVE EDFMT391737 34 FXSQ80PAVE 3D095851A...

Страница 37: ...FXSQ PAVE EDFMT391737 35 FXSQ100PAVE 3D095852A...

Страница 38: ...FXSQ PAVE EDFMT391737 36 FXSQ125PAVE 3D095853A...

Страница 39: ...FXSQ PAVE EDFMT391737 37 FXSQ140PAVE 3D095854A...

Страница 40: ...FXSQ PAVE EDFMT391737 38 11 Sound Levels FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE 4D095804B 4D095805B...

Страница 41: ...FXSQ PAVE EDFMT391737 39 FXSQ40PAVE FXSQ50PAVE 4D095806B 4D095807B...

Страница 42: ...FXSQ PAVE EDFMT391737 40 FXSQ63PAVE FXSQ80PAVE 4D095808B 4D095809B...

Страница 43: ...FXSQ PAVE EDFMT391737 41 FXSQ100PAVE FXSQ125PAVE 4D095810B 4D095811B...

Страница 44: ...FXSQ PAVE EDFMT391737 42 FXSQ140PAVE 4D095812B...

Страница 45: ...FXSQ PAVE EDFMT391737 43 12 Centre of Gravity FXSQ20PAVE FXSQ25PAVE FXSQ32PAVE FXSQ40PAVE FXSQ50PAVE FXSQ63PAVE FXSQ80PAVE FXSQ100PAVE FXSQ125PAVE FXSQ140PAVE 4D095814B Unit mm...

Страница 46: ...chamber for rear suction Note 1 KDDFP63B80 Long life replacement filter Note 1 KAFP631B80 Service panel White KTBJ25K80W Fresh white KTBJ25K80F Brown KTBJ25K80T Air discharge adapter KDAP25A71A Shiel...

Страница 47: ...roller Wireless Cooling Only BRC4C66 Note 4 Heat Pump BRC4C65 Note 4 Wired BRC1C62 Note 4 Navigation remote controller Wired remote controller BRC1E62 Note 4 5 Simplified remote controller Exposed typ...

Страница 48: ...our local dealer regarding what to do in case of refrigerant leakage When the air conditioner is installed in a small room it is necessary to take proper measures so that the amount of any leaked refr...

Страница 49: ...ng of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the indoor unit Have the customer actually operate the air conditioner while looking at the o...

Страница 50: ...ts or inlets of the indoor and outdoor units blocked with obstacles It may lead to capacity drop due to fan speed drop or malfunction of equipment Does not cool Does not heat Is the external static pr...

Страница 51: ...type lamp is installed If you set the fan speed at thermostat OFF did you explain the set fan speed to the customer Have you handed the operation manual and the installation manual to the customer Ha...

Страница 52: ...ng framework reinforcement may be required in order to keep the ceiling horizontal and prevent ceiling vibration after opening the ceiling holes For details consult your building and upholstery work c...

Страница 53: ...3 Check the level of the unit Refer to Fig 8 4 Remove the washer clamp 9 used for preventing the washer for hanger 11 from dropping and tighten the up per side nut Hanger Bottom of product Level Viny...

Страница 54: ...t into the clearance between the hanger and the washer for hanger 11 Unless the washers are properly attached the hanging bolts may come off from the hanger WARNING The indoor unit must be securely in...

Страница 55: ...t drainage is ensured Select the piping diameter equal to or larger than except for riser that of the connection piping polyvi nyl chloride piping nominal diameter 25 mm outside diameter 32 mm Install...

Страница 56: ...up grade so that air may not stagnate in the drain hose If air stagnates the drain may ow oppositely when the drain pump stops and generate abnormal sound unit mm Fig 16 Downward inclination of 1 100...

Страница 57: ...ghtened Wrap the sealing material Large 6 so that the metal clamp 1 end side may be doubled Metal clamp 1 accessory Drain hose 2 accessory Sealing material Large 6 accessory Sealing material Large 6 a...

Страница 58: ...Q80PAVE 1 8 15 0 230 1 5 FXSQ100PAVE 2 5 15 0 300 2 0 FXSQ125PAVE 2 8 15 0 300 2 2 FXSQ140PAVE 3 1 15 0 350 2 5 8 DUCT WORK Pay the utmost attention to the following items and conduct the ductwork Che...

Страница 59: ...WARNING When wiring form the wirings orderly so that the control box lid can be securely fastened If the control box lid is not in place the wirings may come out or be sandwiched by the box and the li...

Страница 60: ...uctions below and perform wiring in the control box F2 T2 P1 P2 F1 T1 Securely x the wiring to the provided wiring xture with the clamp 8 Terminal block X1M for power supply wiring and earth wiring Co...

Страница 61: ...ted In case of ON OFF OPERATION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERATION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SET...

Страница 62: ...is completed on page 3 Check if all the installation and piping works for the air conditioner are completed Check that the outside panel and piping cover of the indoor and outdoor units are closed FIE...

Страница 63: ...power supply wiring to the outdoor unit is not carried out The transmission wiring and the remote controller wiring and FORCED OFF wiring are connected wrongly The transmission wiring is disconnected...

Страница 64: ......

Страница 65: ......

Страница 66: ......

Страница 67: ......

Страница 68: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation...

Отзывы: