• Indoor Units • Concealed Ceiling Unit • FXSQ-MVE9
1
1
• VRV
®
Systems • Indoor Units
4
1
Specifications
Standard Accessories
Operation manual
Installation manual
Paper pattern for installation
Drain hose
Clamp metal
Insulation for fitting
Sealing pads
Clamps
Screws
Washer
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
1-2 Electrical Specifications (50Hz)
FXSQ20MVE9
FXSQ25MVE9
FXSQ32MVE9
FXSQ40MVE9
FXSQ50MVE9
FXSQ63MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
0.5
0.5
0.5
0.6
0.9
1.1
Maximum fuse amps (MFA)
A
15
15
15
15
15
15
Full load amps (FLA)
A
0.4
0.4
0.4
0.5
0.7
0.9
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-2 Electrical Specifications (50Hz)
FXSQ80MVE9
FXSQ100MVE9
FXSQ125MVE9
Power Supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Current
Minimum circuit amps (MCA)
A
1.4
1.5
2.0
Maximum fuse amps (MFA)
A
15
15
15
Full load amps (FLA)
A
1.1
1.2
1.6
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 Technical Specifications
FXSQ80MVE9
FXSQ100MVE9
FXSQ125MVE9