18
|
Electrical installation
Installer and user reference guide
67
FXMA-A
VRV system air conditioner
4P680920-1 – 2022.01
Wire type
Installation method
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
Tightening torques
Wiring
Screw size
Tightening torque
(N•m)
Power supply cable
M4
1.2~1.4
Transmission cable
(indoor↔outdoor)
M3.5
0.79~0.97
User interface cable
▪
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
18.1.3 Specifications of standard wiring components
Component
Power supply
cable
MCA
(a)
" 18‒1 Minimum circuit ampacity"
Voltage
220~240 V/220 V
Phase
1~
Frequency
50/60 Hz
Wire sizes
1.5 mm
2
(3‑core wire)
H07RN-F (60245 IEC 66)
Transmission wiring
For specification refer to the installation
manual of the outdoor unit
User interface cable
0.75 to 1.25 mm
2
(2‑core wire)
H05RN-F (60245 IEC 57)
Length ≤500 m
Recommended field fuse
6 A
Residual current device
Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
indoor unit for exact values).