b. Items to be checked at time of delivery
Also review the “SAFETY CONSIDERATIONS”
Items to be checked
Check
Did you explain about the indoor unit operation while
showing the operation manual to your customer?
Did you hand the operation manual over to your cus-
tomer?
2-3 NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the unit
(especially cleaning filters, operating different functions, and
adjusting the temperature) by having them carry out opera-
tions themselves while looking at the manual.
3. SELECTING INSTALLATION SITE
(1) Select an installation site where the following condi-
tions are satisfied and that meets with your custom
-
er’s approval.
•
The floor is strong enough to bear the indoor unit weight.
•
The floor is not significantly inclined.
•
Nothing blocks the air passage.
•
Condensate can be properly drained.
•
Sufficient clearance for installation and maintenance can
be ensured.
•
Optimum air distribution can be ensured.
•
There is no risk of flammable gas leakage.
•
Piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manu-
al of the outdoor unit.)
WARNING
•
If the supporting structural members are not strong enough
to take the unit’s weight, the unit could fall out of place and
cause serious injury.
•
Do not install unit in an area where flammable materials are
present due to the risk explosion resulting in serious injury
or death.
CAUTION
•
Install the indoor and outdoor units, power supply wiring
and connecting wires at least 3.5 ft. (1 m) away from televi
-
sions or radios in order to prevent image interference or
noise.
(Depending on the radio waves, a distance of 3.5 ft. (1 m)
may not be enough to eliminate the noise.)
Base
FXLQ
Window
4 (100)
or more
(FXLQ)
6 (150)
or more
(FXNQ)
4 (100)
or more
(FXLQ)
3/4 (20) or more
40 (1000)
or more
70 (1750)
or more
Air flow direction
Air inlet
direction
Front side
[unit : in. (mm)]
FXNQ
Maintenance
area
3 1/8 (80) or more
A or more
B or more
24 5/8 (625)
(IMPORTANT) Leave sufficient clearance for air inlet
and maintenance.
[unit: in. (mm)]
Model
A
FXNQ12MVJU
28 (710)
FXNQ18 · 24MVJU
39 (990)
B
46 (1170)
FXNQ07 · 09MVJU
23 (570)
41 (1030)
57 (1450)