CAUTION
•
When conducting wiring work, do not touch the printed circuit
board. It may cause failure.
•
Never connect the power supply wiring to the terminal block
for remote controller/transmission wiring. It may damage the
total system.
•
Do not connect the remote controller/transmission wiring to
the wrong terminal block.
•
In case the piping penetration cover is cut off and used as
wiring penetration hole, after the wiring connection is fin-
ished, mend the cover.
•
Seal the clearance around the wirings with putty and insulat-
ing material (field supply).
(If insects and small animals get into the indoor unit, short cir-
cuiting may occur inside the control box.)
•
If the low voltage wiring (remote controller wiring) and the
high voltage wiring (power supply wiring, earth wiring) are
brought into the indoor unit from the same place, they may be
affected by electric noise (outside noise) and cause malfunc-
tion or failure.
•
Keep the distance of 50mm or more between the low voltage
wiring (remote controller wiring) and the high voltage wiring
(power supply wiring, earth wiring) at anywhere outside the
indoor unit. If both the wirings are laid down together, they
may be affected by electric noise (outside noise) and cause
malfunction or failure.
8-5
EXAMPLE OF WIRING
<< No. 1 system: When 1 remote controller is used for 1
indoor unit. >>
<< No. 2 system: When carrying out group control or 2
remote controller control. >>
Transmission wiring
Remote controller
wiring
Clamp (4)
(accessory)
Power supply
wiring and
Earth wiring
Wiring fixture (11) (accessory)/
Screw for wiring fixture (12)
(accessory)
Wiring fixture (11) (accessory)/
Screw for wiring fixture (12)
(accessory)
(1) Install the fixture at the wiring entrance side.
(2) Fix the wiring to the fixture by clamps so that no tension will
be given to the terminal connection.
(3) To avoid the loosing of the power supply wiring and Earth
wiring, band the clamp to tightly fit the fixture at terminal
block side.
Fig. 32
Power supply wiring
and earth wiring
Remote controller
and transmission wiring
Distance of
50mm betw
een
Resin bushing (10)
(accessory)
Putty or insulation
(field supply)
High voltage wiring
Low voltage wiring
Indoor unit B
Most downstream
Indoor unit
Power supply
220-240V/220V
1 ~
50Hz/60Hz
Power supply
220-240V/220V
1 ~
50Hz/60Hz
Power supply
220-240V/220V
1 ~
50Hz/60Hz
Outdoor
unit
Remote controller
Indoor unit A
(option)
Remote controller
(option)
Remote controller
(option)
L
P2
P1
N
F2
P1
N
F1
IN/D
OUT/D
F1
L
F2 F1 F2
T1 T2
N
L
P2
P2
P1
F2
F1 T1 T2
P2
P1
F2
F1 T1 T2
L N
L N
L N
P1P2
P1P2
L N
P1 P2
P1 P2
F2
N
F1
L
N
L
F1 F2 F1 F2
T1 T2
P1 P2
F2
F1
T1 T2
N
L
IN/D OUT/D
P1 P2
F2
F1
T1 T2
P1 P2
P1 P2
Outdoor
unit
Note) It is not needed to set the indoor unit
address when using group control.
(It is automatically set when the
power is turned on.)
Indoor
unit A
Indoor
unit B
Most down-
stream
indoor unit
For use with 2
remote controllers
Case of group
control
Remote
controller
Remote controller
(option)
Remote
controller
(option)
Power supply
220-240V/220V
1 ~
50Hz/60Hz
01_EN_3P368557-2D.fm Page 13 Wednesday, February 13, 2019 2:46 PM