16
|
Unit installation
Installer and user reference guide
52
FXFN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P677925-1 – 2021.07
▪
safety shut-off valves
▪
safety alarm, in combination with a CO
2
refrigerant leak detector (a safety alarm
alone is NOT considered an appropriate measure where occupants are restricted
in their movements)
▪
CO
2
refrigerant leak detector
WARNING
Install the unit ONLY in locations where the doors of the occupied space are NOT
tight fitting.
WARNING
When using safety shut-off valves, make sure to install measures such as a bypassing
piping with a pressure relief valve (from liquid pipe to gas pipe). When the safety
shut-off valves close and no measures are installed, increased pressure may damage
the liquid piping.
Example:
Install the bypass piping (
e
) with a pressure relief valve (
g
) leading from
the liquid piping between indoor unit and the shut off valve (
c2
) to the gas piping
between outdoor unit and the shut off valve (
d1
).
a
b
f
f
h
g
b c1
c1
c2
c2
d1
d1
d2
d2
ee
ee
Ø12.7 mm
Ø9.52 mm
16‒1 Installation layout example
a
Outdoor unit
b
Stop valve on the outdoor unit
c1
Liquid piping between outdoor unit and the shut off valve
c2
Liquid piping between indoor unit and the shut off valve
d1
Gas piping between outdoor unit and the shut off valve
d2
Gas piping between indoor unit and the shut off valve
e
Bypassing piping
f
Safety shut off valve
g
Pressure relief valve
h
Indoor unit
To determine the minimum number of appropriate measures
For occupancies other than on the lowest underground floor of the building
If the total refrigerant charge (kg)
divided by the room volume
(a)
(m
3
) is…
…the number of appropriate measures
must be at least…
<QLMV
0
>QLMV and <QLAV
1
>QLAV
2
(a)
For occupied spaces with a floor area exceeding 250 m
2
, use 250 m
2
as the floor area for
determination of the room volume (
Example:
even if the room area is 300 m
2
and the
room height is 2.5 m, calculate the room volume as 250 m
2
×2.5 m=625 m
3
)