8 Troubleshooting

Installation and operation manual

12

FXFA20~125A2VEB

VRV system air conditioner

3P599604-1C – 2020.10

NOTICE

▪ Do  NOT  use  gasoline,  benzene,  thinner  polishing

powder  or  liquid  insecticide. 

Possible  consequence:

Discoloration and deformation.

▪ Do  NOT  use  water  or  air  of  50°C  or  higher. 

Possible

consequence: 

Discoloration and deformation.

▪ Do  NOT  scrub  firmly  when  washing  the  blade  with

water. 

Possible  consequence: 

The  surface  sealing

peels off.

Clean with a soft cloth. If it is difficult to remove stains, use water or
neutral detergent.

7.3

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Please contact your installer for more information.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  where  you  purchased  the
unit.

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

7.3.1

About the refrigerant leakage sensor

WARNING

It  is  necessary  to  replace  the  sensor  after  every  detection
or at the end of the lifetime. Authorized person only MUST
replace the sensor.

NOTICE

Functionality  of  the  safety  measures  are  periodically
automatically  checked.  In  case  of  malfunction,  error  code
will display on the user interface.

NOTICE

The  R32  refrigerant  leakage  sensor  is  a  semiconductor
detector  which  may  incorrectly  detect  substances  other
than  R32  refrigerant.  Avoid  using  chemical  substances
(e.g.  organic  solvents,  hair  spray,  paint)  in  high
concentrations,  in  the  close  proximity  of  the  indoor  unit
because  this  may  cause  misdetection  of  the  R32
refrigerant leakage sensor.

INFORMATION

Lifetime  of  the  sensor  is  10  years.  The  user  interface
displays  error  "

CH-05

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-02

"  after  the  end  of  the

sensor lifetime. For more information refer to the reference
guide of the user interface and contact you dealer.

In case of detection when the unit is standby

When the detection occurs when the unit is standby, "false detection
check" will occur.

False detection check

1

Unit starts fan operation on the lowest setting.

2

User  interface  displays  error  code  "

A0-13

",  emits  alarm  sound

and status indicator is blinking.

3

Sensor checks if refrigerant leakage or misdetection occurred.

▪ If refrigerant leakage is NOT detected, 

Result: 

 system returns to

normal operation after approximately 2 minutes.

▪ If refrigerant leakage is detected, 

Result:

1

User  interface  displays  error  "

A0-11

",  emits  alarm  sound  and

status indicator is blinking.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

In case of detection when the unit is turned on

1

User  interface  displays  error  "

A0-11

",  emits  alarm  sound  and

status indicator is blinking.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

INFORMATION

To stop alarm of the user interface see the reference guide
of the user interface.

INFORMATION

The minimum airflow during normal operation or during the
refrigerant leakage detection is always >240 m

3

/h.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Содержание FXFA100A2VEB

Страница 1: ...eration manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFA20A2VEB FXFA25A2VEB FXFA32A2VEB FXFA40A2VEB FXFA50A2VEB FXFA63A2VEB FXFA80A2VEB FXFA100A2VEB FXFA125A2VEB ...

Страница 2: ... fie utilizate în conformitate cu instrucţiunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно н...

Страница 3: ... wiring components 18 14 2 To connect the electrical wiring to the indoor unit 18 15 Commissioning 19 15 1 Checklist before commissioning 19 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 21 17 1 Wiring diagram 21 17 1 1 Unified wiring diagram legend 21 1 About the documentation 1 1 About this document Target audience Authorised installers end users INFOR...

Страница 4: ...per earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete earthing may cause electrical shock Install the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or...

Страница 5: ...on piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansion and contraction of long runs of piping Piping in refrigerating systems shall be designed and installed such as to minimise the likelihood of hydraulic shock damaging the system The indoor equipment and pipes shall be securely mounted and...

Страница 6: ...bol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions for safe operation WARNING Do NOT...

Страница 7: ...ting any maintenance task CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check the unit stand and fit...

Страница 8: ...he unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental refrigerant leaks make sure there are no naked flames The refrigerant itself is entirely safe non toxic and mildly flammable but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters gas cookers etc is present Alw...

Страница 9: ...ooling Heating and Auto operation modes Setback A function that keeps the room temperature in a specific range when the system is turned off by the user the schedule function or the OFF timer 6 2 1 Basic operation modes The indoor unit can operate in various operation modes Icon Operation mode Cooling In this mode cooling will be activated as required by the setpoint or by Setback operation Heatin...

Страница 10: ...fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualified service person to perform this work However as end user you may clean the air filter suction grille air outlet and outside panels WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit ...

Страница 11: ...er interface 7 2 2 To clean the suction grille NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remove the suction grille Standard panel 45 1 2 Design panel 1 2 3 Remove the air filter 1 2 3 4 Clean the suction grille Wash with a soft bristle brush and water or neutral detergent If the suc...

Страница 12: ...time Authorized person only MUST replace the sensor NOTICE Functionality of the safety measures are periodically automatically checked In case of malfunction error code will display on the user interface NOTICE The R32 refrigerant leakage sensor is a semiconductor detector which may incorrectly detect substances other than R32 refrigerant Avoid using chemical substances e g organic solvents hair s...

Страница 13: ...ntling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recovery For the installer 11 About the box 11 1 Indoor unit 11 1 1 To remove the accessories from the indoor unit 1 1 1 8 4 1 1 1 a 4 1 1 7 e f d c b h i m g j k l a Paper pattern for installation upper part...

Страница 14: ...tion before installation Minimum floor area requirements CAUTION The total refrigerant charge in the system cannot exceed the requirements for minimum floor area of the smallest room that is served For minimum floor area requirements for indoor units see the installation and operation manual of the outdoor unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMA...

Страница 15: ...ine the correct vertical position 2 1 2 1 2 1 2 1 A B 1 1 2 C a b c 2 1 2 D A In case of installation with standard decoration panel B In case of installation with fresh air intake kit C In case of installation with self cleaning decoration panel D In case of installation with design decoration panel a Suspended ceiling b Installation guide accessory c Unit Level Make sure the unit is level at all...

Страница 16: ...is less than 4 mm from the metal clamp part 3 Check for water leaks see To check for water leaks 416 4 Install the insulation piece drain pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with tie wraps 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain ...

Страница 17: ...rial Phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping temper grade and thickness Outer diameter Ø Temper grade Thickness t a 6 4 mm 1 4 Annealed O 0 8 mm t Ø 9 5 mm 3 8 12 7 mm 1 2 15 9 mm 5 8 a Depending on the applicable legislation and the maximum working pressure of the unit see PS High on the unit name plate larger piping thickness might be requir...

Страница 18: ...current device Must comply with applicable legislation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of indoor unit for exact values 14 2 To connect the electrical wiring to the indoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover For instructions on how to connect the optional equipment see the instal...

Страница 19: ...e system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipe...

Страница 20: ...tion in the room It determines the interval at which Time to clean filter notification is displayed on the user interface If you want an interval of air contamination Then 1 M SW 2500 h light 10 20 0 01 1250 h heavy 02 Notification ON 3 01 Notification OFF 02 Setting Thermostat sensor selection This setting must correspond with how if the remote controller thermostat sensor is used When the remote...

Страница 21: ... earth Connection Protective earth screw Connector A Rectifier Earth Relay connector Field wiring Short circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip Symbol Meaning Symbol Meaning OUTDOOR Outdoor unit Wire clamp Residual current device Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White YLW Yellow Symb...

Страница 22: ...G Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor ...

Страница 23: ......

Страница 24: ...3P599604 1C 2020 10 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Отзывы: