Installation and operation manual
1
25M9V3B9
VRV System air conditioners
3P468515-3 – 12.2016
C
ONTENTS
Page
Before installation.............................................................................. 1
Important information regarding the refrigerant used........................ 2
Selecting installation site................................................................... 2
Preparations before installation......................................................... 2
Indoor unit installation ....................................................................... 2
Refrigerant piping work ..................................................................... 3
Drain piping work .............................................................................. 3
Electric wiring work ........................................................................... 4
Wiring example and how to set the remote controller ....................... 4
Wiring example ................................................................................. 4
Field setting....................................................................................... 5
Test operation.................................................................................... 6
Special features ................................................................................ 6
Maintenance...................................................................................... 7
Disposal requirements ...................................................................... 7
Wiring diagram .................................................................................. 8
B
EFORE
INSTALLATION
■
Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
■
Refer to the installation manual of the outdoor unit for items not
described in this manual.
■
Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.
■
Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.
Precautions
■
Do not install or operate the unit in rooms mentioned below:
•
Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
•
Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
•
Where volatile flammable gas like thinner or gasoline is used.
•
Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
•
Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.
■
Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.
Accessories
Check if the following accessories are included with your unit.
Optional accessories
■
There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
■
Wiring adaptor for electrical heater.
For the following items, take special care during
construction and check after installation is finished
Notes to the installer
■
Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.
■
Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.
FXDQ20M9V3B9
FXDQ25M9V3B9
VRV System air conditioners
Installation and
operation manual
READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE
AND INFORMATION.
Installation and
operation manual
Fuse
Caution for
servicing sticker
Suction air
filter
Tick
✓
when
checked
■
Is the indoor unit fixed firmly?
The unit may drop, vibrate or make noise.
■
Is the gas leak test finished?
It may result in insufficient cooling.
■
Is the unit fully insulated?
Condensate water may drip.
■
Does drainage flow smoothly?
Condensate water may drip.
■
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
■
Are wiring and piping correct?
The unit may malfunction or components may burn out.
■
Is the unit safely grounded?
Dangerous at electric leakage.
■
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
■
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling.
■
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
Installation and oper
ation m
an
ual
VR
V S
ystem
air cond
itio
ner
s
Содержание FXDQ20M9V3B9
Страница 1: ...INSTALLATION AND OPERATION MANUAL FXDQ20M9V3B9 FXDQ25M9V3B9 System air conditioners...
Страница 2: ...1 1 7 7 2 2 4 4 3 3 1 2 3 5a 5a 6 6 5b 5b...
Страница 12: ......
Страница 13: ......
Страница 14: ......
Страница 16: ...3P468515 3 12 2016 Copyright 2016 Daikin...