English
1-9
IMPORTANT:
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and/or national codes and regulations. They are also subject to the type of installation and
size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated
in the fixed wiring in accordance with the relevant local and national legislation.
FWC 03/04/06/07/09/11/12/14/16C (with controller)
X1
3WV
Chiller
VALVE
L
N
220-240V/~/50Hz or
208-230V/~/60Hz
L
N
X2
3WV
VALVE
L
N
220-240V/~/50Hz or
208-230V/~/60Hz
L
N
X3
3WV
VALVE
L
N
220-240V/~/50Hz or
208-230V/~/60Hz
L
N
3WV
3 way valve
Field supply
X1, X2, X3, Relay (220-240V, 10A)
FCU 1
FCU 2
FCU 3
Note:
This is a proposed wiring connection. It may change subject to the chiller unit and must comply with the local and national
code and regulations.
Model
Indoor
FWC03C
FWC04C
FWC06C
FWC07C
Voltage Range**
Indoor
220V-240V/ ~ /50Hz +
!
or 208V-230V/ ~ /60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.5
3
1.5
3
1.5
3
1.5
3
Recommended Time Delay Fuse*
A
1
1
1
2
Model
Indoor
FWC09C
FWC11C
FWC12C
FWC14C
FWC16C
Voltage Range**
Indoor
220V-240V/ ~ /50Hz +
!
or 208V-230V/ ~ /60Hz +
!
Power Supply Cable Size*
mm
2
Number of Conductors
1.5
3
1.5
3
1.5
3
1.5
3
1.5
3
Recommended Time Delay Fuse*
A
3
5
5
5
5
!
There must be an all pole
disconnection in the supply mains
with a contact separation of at
least 3mm.
All power line must be from the
same phase.
1 IM-CCCW-0314(1)DAIKIN-EN.indd 9
1 IM-CCCW-0314(1)DAIKIN-EN.indd 9
1/30/15 11:53:44 AM
1/30/15 11:53:44 AM
Содержание FWC03C
Страница 87: ...CVR IM CCCW 0314 2 DAIKIN EN ind3 3 CVR IM CCCW 0314 2 DAIKIN EN ind3 3 3 24 16 9 11 40 AM 3 24 16 9 11 40 AM...
Страница 88: ...CVR IM CCCW 0314 2 DAIKIN EN ind4 4 CVR IM CCCW 0314 2 DAIKIN EN ind4 4 3 24 16 9 11 41 AM 3 24 16 9 11 41 AM...
Страница 103: ...CVR IM CCCW 0314 2 DAIKIN_AR ind2 2 CVR IM CCCW 0314 2 DAIKIN_AR ind2 2 3 24 16 9 10 33 AM 3 24 16 9 10 33 AM...