Installing indoor unit.

3-1. Right-side, right-back, or right-bottom piping.

1) Attach the drain hose to the underside of the refrigerant pipes with 

adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with insulation 

tape.

3) Pass the drain hose and refrigerant pipes through the wall hole, 

then set the indoor unit on the mounting plate hooks by using the 

 markings at the top of the indoor unit as a guide.

4) Open the front panel, then open the service lid. 

(Refer to Installation Tips)

5) Pass the interconnecting wires from the outdoor unit through the 

feed-through wall hole and then through the back of the indoor 
unit. Pull them through the front side.  Bend the ends of tie wires 
upward in advance for easier work. (If the interconnecting wire 
ends are to be stripped first, bundle wire ends with adhesive 
tape.)

6) Press the indoor unit’s bottom panel with both hands to set it 

on the mounting plate hooks. Make sure the wires do not catch 
on the edge of the indoor unit.

3-2. Left-side, left-back, or left-bottom piping.

1) Attach the drain hose to the underside of the refrigerant pipes 

with adhesive vinyl tape.

2) Be sure to connect the drain hose to the drain port in place of a 

drain plug.

3) Shape the refrigerant pipe along the pipe 

path marking on the mounting plate.

4) Pass drain hose and refrigerant pipes 

through the wall hole, then set the indoor 
unit on mounting plate hooks, using the 

 markings at the top of indoor unit as a 

guide.

5) Pull in the interconnecting wires.
6) Connect the inter-unit piping.

Right-bottom

piping

Right-back piping

Bind coolant pipe

and drain hose

together with

insulating tape.

Remove pipe port cover

here for right-side piping

Remove pipe port cover

here for right-bottom piping

Mounting plate

A

Wire guide

When stripping the 
ends of interconnecting 
wires in advance, bind 
right ends of wires with 
insulating tape.

Hang indoor unit’s hook here.

Interconnecting
wires

Mounting plate

A

Remove pipe port cover here for left-bottom piping

Remove pipe

port cover

here for left-

side piping

Left-bottom piping

Left-side

piping
Left-back

piping

No gap

Do not apply lubricating 
oil (refrigerant machine 
oil) when inserting.
Application of causes 
deterioration and drain 
leakage of the plug.

Insert a hexagon wrench (4mm)

How to set drain plug

Interconnecting wires

Drain hose

Caulk this hole 
with putty or 
caulking material.

Wrap insulating tape around the 
bent portion of refrigerant pipe.
Overlap at least half the width of 
the tape with each turn.

Bind with 
plastic tape.

Thermistor cable

 A  Mounting plate

01_EN_3P147083-2F.fm  Page 6  Friday, October 28, 2005  9:29 AM

Содержание FTYN25DV3B ATY20DV2

Страница 1: ...Portugues T rk e Deutsch English Installationsanleitung Split Baureihe R410A Montaj k lavuzlar R410A Split serisi Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual...

Страница 2: ...51 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4...

Страница 3: ...cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After al...

Страница 4: ...ation manual 1 Wireless remote controller 1 Indoor unit fixing screw M4 12L 2 Drain plug Heat pump Models 1 The indoor unit should be sited in a place where the restrictions on installation specified...

Страница 5: ...ew on the service lid Slide the lid downward to remove it How to attach the service lid Insert the upper part of the service lid into the outdoor unit to install Tighten the screws This service lid is...

Страница 6: ...r unit at a site where the suction side may be exposed directly to wind 3 To prevent exposure to wind it is recommended to install a baffle plate on the air discharge side of the outdoor unit 4 In hea...

Страница 7: ...leakage 1 Bore a feed through hole of 65mm in the wall so it has a down slope toward the outside 2 Insert a wall pipe into the hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant...

Страница 8: ...the drain port in place of a drain plug 3 Shape the refrigerant pipe along the pipe path marking on the mounting plate 4 Pass drain hose and refrigerant pipes through the wall hole then set the indoor...

Страница 9: ...ing diagram included with the product for details on the fuse specifications Do not turn ON the safety breaker until all work is completed 1 Strip wire ends 15mm 2 Match wire colours with terminal num...

Страница 10: ...e attached to the indoor unit as with embedded piping work use any commercially available drain socket nominal diameter 13mm as a joint FTN 1 2 3 4 Terminal block Electrical component box Wire retaine...

Страница 11: ...tion of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 t...

Страница 12: ...gauge manifold to gas shut off valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no op...

Страница 13: ...r Unit 4 Wiring Gas shut off valve Liquid shut off valve Valve lid Hexagonal wrench Close FTYN Thermistor L N 3 2 1 4 5 Firmly secure wire retainer so wire terminations will not receive external stres...

Страница 14: ...wire stop FTN Thermistor Firmly secure wire retainer so wire terminations will not receive external stress Use the specified wire type and connect it securely To connect the wires remove the screw an...

Страница 15: ...anual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for s...

Страница 16: ...0511 HT 3P147083 2F M05B073...

Отзывы: