background image

8 Finishing the indoor unit installation

Installation manual

9

FTXTA30C2V1B(W)(B)
Daikin room conditioner
3P697375-7H – 2023.09

a

a

S21 connector

3

Put  the  electrical  wiring  box  cover  back  and  pull  the  wire
harness around it as shown in the figure above.

8

Finishing the indoor unit
installation

8.1

To insulate the drain piping,
refrigerant piping and
interconnection cable

f

g
h

a

b

c
d

e

a

Slit

b

Heat insulation pipe cover

c

Liquid pipe

d

Gas pipe

e

Drain pipe

f

Interconnection wire

g

Insulation tape

h

Vinyl tape

1

After the drain piping, refrigerant piping and the electrical wiring
are finished. Wrap refrigerant piping, interconnection cable and
drain  hose  together  using  insulation  tape.  Overlap  at  least  half
the width of the tape with each turn.

d

e

c

b

f

a

a

Drain hose

b

Interconnection cable

c

Mounting plate (accessory)

d

Refrigerant piping

e

Indoor unit fixing screw M4×12L (accessory)

f

Bottom frame

8.2

To pass the pipes through the wall
hole

1

Shape the refrigerant pipes along the pipe path marking on the
mounting plate.

c

c

d

e

a

b

a

Drain hose

b

Caulk this hole with putty or caulking material

c

Adhesive vinyl tape

d

Insulation tape

e

Mounting plate (accessory)

NOTICE

▪ Do NOT bend refrigerant pipes.

▪ Do  NOT  push  the  refrigerant  pipes  onto  the  bottom

frame or the front grille.

2

Pass the drain hose and refrigerant piping through the wall hole
and seal the gap with a putty.

8.3

To fix the unit on the mounting
plate

1

Set  the  indoor  unit  on  the  mounting  plate  hooks.  Use  the  " "
marks as a guide.

2

Press the bottom frame of the unit with both hands to set it on
the  bottom  hooks  of  the  mounting  plate.  Make  sure  that  the
wires do NOT get squeezed anywhere.

Note: 

  Take  care  that  the  interconnection  cable  does  NOT  get

caught in the indoor unit.

3

Press the bottom edge of the indoor unit with both hands until it
is firmly caught by the mounting plate hooks.

4

Secure the indoor unit to the mounting plate using 2 indoor unit
fixing screws M4×12L (accessory).

9

Configuration

INFORMATION

In case 2 indoor units are installed in 1 room, set different
addresses for 2 user interfaces. For procedure refer to the
installer  reference  guide,  for  location  see 

"1.1  About  this

document"

 [

4

 2].

Содержание FTXTA30C2V1BB

Страница 1: ...Installation manual Daikin room conditioner English Installation manual Daikin room conditioner FTXTA30C2V1BW FTXTA30C2V1BB...

Страница 2: ...mote control 10 11 Disposal 10 12 Technical data 10 12 1 Wiring diagram 10 12 1 1 Unified wiring diagram legend 10 1 About the documentation 1 1 About this document WARNING Make sure installation serv...

Страница 3: ...n site and all electrical construction MUST comply with the applicable legislation WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NO...

Страница 4: ...rsons using cardiac pacemakers or defibrillators This product may cause electromagnetic interference Auto control equipment E g automatic doors or fire alarm equipment This product may cause faulty be...

Страница 5: ...a a a a h 610 605 555 k j i a Recommended mounting plate fixing spots g Value for tape measure b Pocket for the pipe port cover h Position for tape measure at symbol c Use tape measure as shown i Drai...

Страница 6: ...side left back or left bottom INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fi...

Страница 7: ...as possible 1 Connect refrigerant piping to the unit using flare connections 2 Wrap the refrigerant piping connection using vinyl tape overlapping at least half the width of the tape with each turn Ke...

Страница 8: ...ce between both wirings should ALWAYS be at least 50 mm Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice 1...

Страница 9: ...the pipe path marking on the mounting plate c c d e a b a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate accessory NOTICE Do NOT...

Страница 10: ...the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liquid on the outdoor unit are fully open 10...

Страница 11: ...KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of pas...

Страница 12: ...3P697375 7H 2023 09 Copyright 2023 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: