Introduction
SiUS04-702
viii
1.1.2 Cautions Regarding Safety of Users
Warning
Be sure to use parts listed in the service parts list of the applicable model and
appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools may cause an electrical shock,
excessive heat generation or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires may cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it may cause an electrical shock,
excessive heat generation or fire.
Be sure to use an exclusive power circuit for the equipment, and follow the local
technical standards related to the electrical equipment, the internal wiring
regulations, and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work may cause an
electrical shock or fire.
Be sure to use the specified cable for wiring between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections may cause excessive heat generation or fire.
When wiring between the indoor and outdoor units, make sure that the terminal
cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section may cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable may cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
may damage the cable.
Do not mix air or gas other than the specified refrigerant (R410A / R22) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leaking point and repair it
before charging the refrigerant. After charging refrigerant, make sure that there
is no refrigerant leak.
If the leaking point cannot be located and the repair work must be stopped, be
sure to perform pump-down and close the service valve, to prevent the
refrigerant gas from leaking into the room. The refrigerant gas itself is
harmless, but it may generate toxic gases when it contacts flames, such as fan
and other heaters, stoves and ranges.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment may fall and cause injury.
Содержание FTXS09DVJU
Страница 1: ...SiUS04 702 Applied Models z Inverter Pair Heat Pump Inverter Pair Wall Mounted Type D Series...
Страница 12: ...SiUS04 702 List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Страница 14: ...SiUS04 702 Specifications 3 Part 2 Specifications 1 Specifications 4...
Страница 76: ...SiUS04 702 Instruction Operation Manual 65 2 2 FTXS09 12DVJU 2 2 1 Names of Parts...
Страница 77: ...Instruction SiUS04 702 66 Operation Manual...
Страница 78: ...SiUS04 702 Instruction Operation Manual 67...
Страница 79: ...Instruction SiUS04 702 68 Operation Manual 2 2 2 Preparation before Operation...
Страница 80: ...SiUS04 702 Instruction Operation Manual 69...
Страница 81: ...Instruction SiUS04 702 70 Operation Manual...
Страница 82: ...SiUS04 702 Instruction Operation Manual 71 2 2 3 AUTO DRY COOL HEAT FAN Operation...
Страница 83: ...Instruction SiUS04 702 72 Operation Manual...
Страница 84: ...SiUS04 702 Instruction Operation Manual 73 2 2 4 Adjusting the Airflow Direction...
Страница 85: ...Instruction SiUS04 702 74 Operation Manual...
Страница 86: ...SiUS04 702 Instruction Operation Manual 75 2 2 5 POWERFUL Operation...
Страница 87: ...Instruction SiUS04 702 76 Operation Manual 2 2 6 OUTDOOR UNIT QUIET Operation...
Страница 88: ...SiUS04 702 Instruction Operation Manual 77 2 2 7 HOME LEAVE Operation...
Страница 89: ...Instruction SiUS04 702 78 Operation Manual...
Страница 90: ...SiUS04 702 Instruction Operation Manual 79 2 2 8 INTELLIGENT EYE Operation...
Страница 91: ...Instruction SiUS04 702 80 Operation Manual...
Страница 92: ...SiUS04 702 Instruction Operation Manual 81 2 2 9 TIMER Operation...
Страница 93: ...Instruction SiUS04 702 82 Operation Manual...
Страница 94: ...SiUS04 702 Instruction Operation Manual 83 2 2 10 Care and Cleaning...
Страница 95: ...Instruction SiUS04 702 84 Operation Manual...
Страница 96: ...SiUS04 702 Instruction Operation Manual 85...
Страница 97: ...Instruction SiUS04 702 86 Operation Manual...
Страница 98: ...SiUS04 702 Instruction Operation Manual 87...
Страница 99: ...Instruction SiUS04 702 88 Operation Manual...
Страница 100: ...SiUS04 702 Instruction Operation Manual 89 3P141693 1K...
Страница 101: ...Instruction SiUS04 702 90 Operation Manual 2 3 FTXS15 18 24DVJU 2 3 1 Names of Parts...
Страница 102: ...SiUS04 702 Instruction Operation Manual 91...
Страница 103: ...Instruction SiUS04 702 92 Operation Manual...
Страница 104: ...SiUS04 702 Instruction Operation Manual 93 2 3 2 Preparation before Operation...
Страница 105: ...Instruction SiUS04 702 94 Operation Manual...
Страница 106: ...SiUS04 702 Instruction Operation Manual 95...
Страница 107: ...Instruction SiUS04 702 96 Operation Manual 2 3 3 AUTO DRY COOL HEAT FAN Operation...
Страница 108: ...SiUS04 702 Instruction Operation Manual 97...
Страница 109: ...Instruction SiUS04 702 98 Operation Manual 2 3 4 Adjusting the Airflow Direction...
Страница 110: ...SiUS04 702 Instruction Operation Manual 99...
Страница 111: ...Instruction SiUS04 702 100 Operation Manual 2 3 5 POWERFUL Operation...
Страница 112: ...SiUS04 702 Instruction Operation Manual 101 2 3 6 OUTDOOR UNIT QUIET Operation...
Страница 113: ...Instruction SiUS04 702 102 Operation Manual 2 3 7 HOME LEAVE Operation...
Страница 114: ...SiUS04 702 Instruction Operation Manual 103...
Страница 115: ...Instruction SiUS04 702 104 Operation Manual 2 3 8 INTELLIGENT EYE Operation...
Страница 116: ...SiUS04 702 Instruction Operation Manual 105...
Страница 117: ...Instruction SiUS04 702 106 Operation Manual 2 3 9 TIMER Operation...
Страница 118: ...SiUS04 702 Instruction Operation Manual 107...
Страница 119: ...Instruction SiUS04 702 108 Operation Manual 2 3 10 Care and Cleaning...
Страница 120: ...SiUS04 702 Instruction Operation Manual 109...
Страница 121: ...Instruction SiUS04 702 110 Operation Manual...
Страница 122: ...SiUS04 702 Instruction Operation Manual 111 2 3 11 Troubleshooting...
Страница 123: ...Instruction SiUS04 702 112 Operation Manual...
Страница 124: ...SiUS04 702 Instruction Operation Manual 113...
Страница 125: ...Instruction SiUS04 702 114 Operation Manual 3P141693 2K...
Страница 191: ...Check SiUS04 702 180 Service Diagnosis...
Страница 247: ...RX09 12FVJU SiUS04 702 236 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points...
Страница 254: ...SiUS04 702 RX09 12FVJU Removal Procedure 243 5 Pull the sound blanket bottom out Step Procedure Points...
Страница 259: ...RX09 12FVJU SiUS04 702 248 Removal Procedure 4 Lift the compressor up and remove it Step Procedure Points...
Страница 290: ...SiUS04 702 Others 279 Part 8 Others 1 Others 280 1 1 Test Run from the Remote Controller 280 1 2 Jumper Settings 281...
Страница 293: ...Others SiUS04 702 282 Others...
Страница 305: ...SiUS04 702 vi Index...