manualshive.com logo in svg
background image

Installer reference guide 

Daikin room air conditioner

FTXP50M2V1B
FTXP60M2V1B
FTXP71M2V1B

FTXF20A2V1B
FTXF25A2V1B
FTXF35A2V1B
FTXF50A2V1B
FTXF60A2V1B
FTXF71A2V1B

ATXF50A2V1B
ATXF60A2V1B
ATXF71A2V1B

Содержание FTXP50M2V1B

Страница 1: ...Installer reference guide Daikin room air conditioner FTXP50M2V1B FTXP60M2V1B FTXP71M2V1B FTXF20A2V1B FTXF25A2V1B FTXF35A2V1B FTXF50A2V1B FTXF60A2V1B FTXF71A2V1B ATXF50A2V1B ATXF60A2V1B ATXF71A2V1B...

Страница 2: ...remove the front panel 23 6 2 2 To re install the front panel 24 6 2 3 To remove the front grille 24 6 2 4 To re install the front grille 24 6 2 5 To remove the electrical wiring box cover 24 6 2 6 T...

Страница 3: ...fix the unit on the mounting plate 38 7 Configuration 39 7 1 To set a different address 39 8 Commissioning 41 8 1 Overview Commissioning 41 8 2 Checklist before commissioning 41 8 3 To perform a test...

Страница 4: ...d installer 1 1 1 Meaning of warnings and symbols DANGER Indicates a situation that results in death or serious injury DANGER RISK OF ELECTROCUTION Indicates a situation that could result in electrocu...

Страница 5: ...ediately after operation It could be too hot or too cold Give it time to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNIN...

Страница 6: ...necessary guidance for this logbook 1 2 2 Installation site Provide sufficient space around the unit for servicing and air circulation Make sure the installation site withstands the weight and vibrat...

Страница 7: ...lation of pipework shall be kept to a minimum WARNING If appliances contain R32 refrigerant the floor area of the room in which the appliances are installed operated and stored MUST be larger than the...

Страница 8: ...raph or table to determine the minimum floor area 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 310 320 330 340 350 360 370 380 390 4...

Страница 9: ...4 10 9 7 0 46 3 3 6 12 3 7 2 49 0 3 8 13 7 7 4 51 8 4 0 15 1 7 6 54 6 4 2 16 7 7 8 57 5 4 4 18 3 7 956 59 9 Wall mounted unit b m kg Amin m2 Floor standing unit c m kg Amin m2 m Total refrigerant char...

Страница 10: ...NOT charge more than the specified amount of refrigerant When the refrigerant system is to be opened refrigerant MUST be treated according to the applicable legislation WARNING Make sure there is no...

Страница 11: ...erature inside the unit can get much higher than that of the room e g 70 C In case of a brine leak hot parts inside the unit can create a hazardous situation WARNING The use and installation of the ap...

Страница 12: ...so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric noise to avoid unnecessary opening of...

Страница 13: ...mponents box is connected securely Make sure all covers are closed before starting up the unit NOTICE Only applicable if the power supply is three phase and the compressor has an ON OFF starting metho...

Страница 14: ...unit Indoor unit installation manual Installation instructions Format Paper in the box of the indoor unit Installer reference guide Preparation of the installation good practices reference data Format...

Страница 15: ...out Operation range Preparation What to do and know before going on site Installation What to do and know to install the system Configuration What to do and know to configure the system after it is in...

Страница 16: ...n mind At delivery the unit MUST be checked for damage Any damage MUST be reported immediately to the claims agent of the carrier Bring the packed unit as close as possible to its final installation p...

Страница 17: ...ries located at the bottom of the package 2 2 2 1 1 1 1 1 1 e d b a c f g h i a Installation manual b Operation manual c General safety precautions d Titanium apatite deodorizing and silver particle f...

Страница 18: ...rant piping drain hose and interconnection cable f Insulation tape 4 2 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation Operation mode O...

Страница 19: ...an operating electric heater 5 2 1 Installation site requirements of the indoor unit INFORMATION Also read the precautions and requirements in the General safety precautions chapter INFORMATION The so...

Страница 20: ...path of direct sunlight In bathrooms Sound sensitive areas e g near a bedroom so that the operation noise will cause no trouble WARNING Do NOT place objects below the indoor and or outdoor unit that...

Страница 21: ...iping thickness might be required 5 3 2 Refrigerant piping insulation Use polyethylene foam as insulation material with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with...

Страница 22: ...sharp edges or piping particularly on the high pressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical sh...

Страница 23: ...ing 7 Finishing the outdoor installation 8 Finishing the indoor installation INFORMATION For installation of the outdoor unit mounting the outdoor unit connecting the refrigerant piping to the outdoor...

Страница 24: ...the front grille 3 Push down the 3 upper hooks marked with a symbol with 3 circles a b a a Upper hook b Symbol with 3 circles 4 We recommend opening the flap before removing the front grille 5 Place b...

Страница 25: ...the service cover horizontally away from the unit a b a Service cover screw b Service cover 6 3 Installing the indoor unit 6 3 1 Precautions when installing the indoor unit INFORMATION Also read the p...

Страница 26: ...f a A Mounting plate for class 20 35 B Mounting plate for class 50 71 a Recommended mounting plate fixing spots b Pocket for the pipe port cover c Tabs for placing a spirit level d Through the wall ho...

Страница 27: ...pe port cover MUST be removed 1 Cut off the pipe port cover from inside the front grille using a coping saw 2 Remove any burrs along the cut section using a half round needle file NOTICE Do NOT use ni...

Страница 28: ...inyl chloride pipe When connecting a rigid polyvinyl chloride pipe nominal 13 mm directly to the drain hose as with embedded piping work use a field supplied drain socket nominal 13 mm a b c 18 a Drai...

Страница 29: ...om INFORMATION The factory default is right side piping For left side piping remove the piping from the right side and install it on the left side 1 Remove the insulation fixing screw on the right sid...

Страница 30: ...leaks 6 4 Connecting the refrigerant piping 6 4 1 About connecting the refrigerant piping Before connecting the refrigerant piping Make sure the outdoor and indoor unit are mounted Typical workflow C...

Страница 31: ...llations to withstand the pressure and to prevent foreign materials e g mineral oils and moisture from mixing into the system Install the piping so that the flare is NOT subjected to mechanical stress...

Страница 32: ...6 4 4 Pipe bending guidelines Use a pipe bender for bending All pipe bends should be as gentle as possible bending radius should be 30 40 mm or larger 6 4 5 To flare the pipe end CAUTION Incomplete fl...

Страница 33: ...rant piping to the unit using flare connections Insulation Insulate the refrigerant piping interconnection cable and drain hose on the indoor unit as follows c a b f d g e a Gas pipe b Gas pipe insula...

Страница 34: ...qualified persons in order to avoid a hazard WARNING Do NOT connect the power supply to the indoor unit This could result in electrical shock or fire WARNING Do NOT use locally purchased electrical pa...

Страница 35: ...Item Tightening torque N m M4 X1M 1 2 M4 earth The earth wire between the wire retainer and the terminal must be longer than the other wires 1 3 6 5 4 Specifications of standard wiring components Com...

Страница 36: ...upply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to pre...

Страница 37: ...adapter b S21 wire harness routing for other applications c S21 connector 3 Put the electrical wiring box cover back and pull the wire harness around it as shown in the previous figure 6 6 Finishing t...

Страница 38: ...o the bottom frame or the front grille 2 Pass the drain hose and refrigerant pipes through the wall hole 6 6 3 To fix the unit on the mounting plate 1 Set the indoor unit on the mounting plate hooks U...

Страница 39: ...to damage any of the surrounding parts when cutting the address jumper 3 Turn the power supply on Result The flap of the indoor unit will open and close to set the reference position INFORMATION For F...

Страница 40: ...s the indoor unit ON OFF switch while the operation indicator is blinking Jumper Address Factory setting 1 After cutting with nippers 2 INFORMATION If the setting could NOT be completed while the oper...

Страница 41: ...he unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Make sure...

Страница 42: ...eating mode 20 24 C 3 The system stops operating 3 minutes after the unit is turned OFF 8 3 1 To perform a test run in winter season When operating the air conditioner in Cooling mode in winter set it...

Страница 43: ...ates properly please make sure the following is clear for the user Make sure that the user has the printed documentation and ask him her to keep it for future reference Inform the user that he can fin...

Страница 44: ...conditioner 4P513661 8H 2019 12 10 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable l...

Страница 45: ...iagram legend For applied parts and numbering refer to the wiring diagram on the unit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by i...

Страница 46: ...emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Re...

Страница 47: ...nsor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrester SR WLU Signal receiver SS Selector switch SHEET METAL...

Страница 48: ...ain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or application explaining how to operate it Maintenan...

Страница 49: ......

Страница 50: ......

Страница 51: ......

Страница 52: ...4P513661 8H 2019 12 Copyright 2018 Daikin Verantwortung f r Energie und Umwelt...

Отзывы: