Indoor Unit Installation
1.
Installing the mounting plate
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
1)Temporarily secure the mounting plate to the wall, make sure that the plate is completely level, and mark the drilling points
on the wall.
2)Secure the mounting plate to the wall with screws.
Recommended mounting plate retention spots and dimensions
09/12 class
18/24 class
Recommended mounting plate
retention spots (7 spots in all)
Place a leveler
on these tabs.
Use a tape measure as
shown.
Position the end of the
tape measure at .
Drain hose
position
Through-the-wall
hole
φ
2-9/16 (65)
Place the pipe port
cover in this pocket.
Gas pipe end
Liquid pipe end
* Depending on the model, the actual distance between the liquid pipe end and gas pipe end may differ from the distance between those symbols on the
mounting plate (the distance listed in this manual).
Always measure the actual distance between the liquid pipe end and gas pipe end before installing refrigerant pipes.
4-5/8 (118)
4-3/4 (120)
11-3/4 (299)
36-1/4 (920)
1-7/8 (47)
1-7/8 (47)
6-5/16 (160)
6-5/16 (160)
15-7/16 (392)
2-9/16 (65*)
15-7/16 (392)
2-11/16 (68)
6-1/4 (158)
11-1/2 (292)
15-1/4 (387)
2-11/16 (68)
5-7/8 (150)
9-1/16 (230)
4-3/4 (120)
2-3/8 (60)
unit: inch (mm)
Through-the-wall
hole
φ
3-1/8 (80)
Gas pipe end
Liquid pipe end
Place a leveler
on these tabs.
Drain hose
position
4-3/4 (120)
Recommended mounting
plate retention spots
(7 spots in all)
11-3/4 (299)
2-9/16 (65*)
1-7/8 (47)
4-3/4 (120)
5-7/8 (150)
2-3/8 (60)
4-5/8 (118)
9-1/16 (230)
43-5/16 (1100)
6-5/16 (160)
21-5/8 (550)
21-5/8 (550)
2-11/16 (68)
15-1/4 (387)
6-5/16 (160)
2-11/16 (68)
1-7/8 (47)
The removed pipe port cover can be kept in the mounting plate pocket.
Mounting
plate
A
Removed pipe
port cover