Service Diagnosis
47
L3
Description
ELECTRICAL BOX TEMPERATURE RISE (COMPRESSOR OFF)
Supposed Cause
1. Fin temperature rise due to defective outdoor unit fan.
2. Fin temperature rise due to short circuit.
3. Fin thermistor defective.
4. Connector in poor contact.
5. Outdoor unit PCB defective.
Troubleshooting
Models
A°C
RXB50/60B
80
ARXN/RXN25/35M
78
ARXN/RXN50/60M
122
Error again?
No
Yes
Check heat sink thermistor
resistance.
Change heat sink or check
outdoor fan condition.
Turn off the unit and turn
on back after 20 mins.
Resistance normal?
Heat sink
temperature >
A
°C?
No
Yes
Outdoor fan
functioning?
Yes
Heat sink dirty?
Yes
Check outdoor fan.
No
No
Clean the heat sink.
No
Change
outdoor
fan motor.
Check
installation
condition.
Change
outdoor
PCB.
Change
thermistor.
*Remark:
Refer to Appendix A for thermistor resistance check procedures.(Page 59, item 6.1)
Refer to Appendix A for outdoor fan system check. (Page 65, item 6.8)
Refer to Appendix A for installation condition check. (Page 65, item 6.7)
Содержание FTXB50BV1B
Страница 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A...
Страница 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M...
Страница 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L...
Страница 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M...