Troubleshooting
SiBE041525F
71
Service Diagnosis
4.18 Position Sensor Abnormality
Error Code
H6
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through
the position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage is not as specified.
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is outside the specified range.
Содержание FTX20K2V1B
Страница 12: ...SiBE041525F 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 15: ...SiBE041525F Specifications 4 Part 2 Specifications 1 Specifications 5...
Страница 16: ...Specifications SiBE041525F 5 Specifications 1 Specifications See corresponding databook...
Страница 51: ...SiBE041525F Remote Controller 40 Part 5 Remote Controller 1 Remote Controller 41...