Troubleshooting
SiMT041509E
69
Service Diagnosis
4.13 DC Fan Lock
Error Code
E7
Method of Error
Detection
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Error Decision
Conditions
The fan does not start in about 30 seconds even when the fan motor is running.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Disconnection of the fan motor
Foreign matter stuck in the fan
Defective fan motor
Defective outdoor unit PCB
Troubleshooting
Check No.16
Refer to P.87
(R21669)
Caution
YES
YES
NO
YES
NO
NO
YES
NO
NO
Turn on the power.
Rotate the fan.
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB (main PCB).
Turn off the power and
reconnect the connector.
Remove the foreign
matters.
Replace the outdoor fan
motor.
Replace the fuse.
Replace the outdoor unit
PCB (main PCB).
Fan motor connector
disconnected?
Foreign matters in or
around the fan?
Replace the outdoor fan
motor.
Fan rotates
smoothly?
Pulse signal generated?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the fuse (
+
) for the
fan motor blown?
+
FU2
Содержание FTK(X)M-P Series
Страница 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45...
Страница 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition...