FMCQ50~125A7VEB
Air conditioning system
4PW47629-1
Installation and operation manual
6
-
Confirm the drain operation looking at the drain socket.
-
After checking the drainage flow, turn off the power,
remove the control box lid and disconnect the power
supply from the terminal again.
-
Reattach the control box lid.
E
LECTRIC
WIRING
WORK
General instructions
■
All field supplied parts and materials and electric works must
conform to local codes.
■
Use copper wire only.
■
Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
■
All wiring must be performed by an authorized electrician.
■
Attach the earth leakage circuit breaker and fuse to the power
supply line.
■
A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
■
This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit is matching properly. If wiring and piping
between the outdoor unit and an indoor unit are mismatched,
the system may cause a malfunction.
■
Be sure to ground the air conditioner.
■
Do not connect the ground wire to:
-
gas pipes: might cause explosions or fire if gas leaks.
-
telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during
lightning storms.
-
plumbing pipes: no grounding effect if hard vinyl piping is
used.
Electrical characteristics
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
Specifications for field supplied fuses and wire
W
IRING
EXAMPLE
AND
HOW
TO
SET
THE
REMOTE
CONTROLLER
How to connect wiring
(See figure 10)
■
Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.
■
Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1,
F2) and remote controller wiring
(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.
■
After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.
■
Attach the control box lid.
Precautions
1
Observe the notes mentioned below when wiring to the power
supply terminal block.
-
Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
-
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
-
When clamping wiring, use the clamps (delivered with the
unit) to prevent outside pressure being exerted on the wiring
connections. Tie up firmly. When doing the wiring, make sure
the wiring is neat and does not cause the control box to stick
up. Close the cover firmly.
Inter unit wiring terminal block (3)
Model
Hz
Volts
Voltage range
FMCQ50~125
50
220-240
min. 198-max. 264
power supply
Fan motor
Model
MCA
MFA
KW
FLA
FMCQ50
0.6
16 A
0.056
0.5
FMCQ60
0.9
16 A
0.056
0.7
FMCQ71
0.9
16 A
0.120
0.7
FMCQ100
1.4
16 A
0.120
1.1
FMCQ125
1.9
16 A
0.120
1.5
NOTE
For details, refer to "Electrical data".
L
N
Power supply wiring
Model
Field fuses
Wire
Size
FMCQ50~125
16 A
H05VV-U3G
Local codes
Transmission wiring
Model
Wire
Size
FMCQ50~125
Sheathed wire (2)
0.75-1.25 mm
2
NOTE
■
For details, refer to
"Wiring example" on page 7
.
■
Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:
•
Outdoor unit - indoor unit: max. 1000 m
(total wiring length: 2000 m)
•
Indoor unit - remote controller: max 500 m
1
2
3
1
Round crimp-style terminal
2
Attach insulation sleeve
3
Wiring