25
Engineering & Physical Data
MODEL
INDOOR
FHYC40EXV1
OUTDOOR
RY35DXV1
RY40DXV1
RY40DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
2937 / 426
CLOSE
kPa / psi
2413 / 350
LOW PRESSURE
SWITCH
TYPE
N/A
OPEN
kPa / psi
N/A
CLOSE
kPa / psi
N/A
PHASE SEQUENCER
N/A
YES
DISC. THERMOSTAT SETTING
°C / F
N/A
N/A
130 / 266
MODEL
INDOOR
FHYC50EXV1
OUTDOOR
R50DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
2937 / 426
CLOSE
kPa / psi
2413 / 350
LOW PRESSURE
SWITCH
TYPE
N/A
OPEN
kPa / psi
N/A
CLOSE
kPa / psi
N/A
PHASE SEQUENCER
YES
DISC. THERMOSTAT SETTING
°C / F
130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_FF_FHC.indb 25
DAIKIN_FF_FHC.indb 25
9/27/2012 2:04:54 PM
9/27/2012 2:04:54 PM