10. FIELD SETTINGS
(1) Make sure the control box lids are closed on the indoor and outdoor units.
(2) Field settings must be made from the remote controller and in accordance with installation con-
ditions.
• Setting can be made by changing the
“
Mode No.
”, “
FIRST CODE NO
.”
and
“
SECOND CODE NO.
”
.
• The
“
Field Settings
”
included with the remote control lists the order of the settings and method of opera-
tion.
10-1 Setting air outlet direction
• For changing air outlet direction (2 or 3 directions), refer to the optional installation manual of the sealing
member of air discharge outlet kit or the service manual.
(SECOND CODE NO. is factory set to
“
01
” for air
outlet
in 4 directions.
)
10-2 Setting for options
• For settings for options, see the installation instructions provided with the option.
10-3 Setting air filter sign
• Remote controllers are equiped with liquid crystal display air filer signs to display the time to clean air fil-
ters.
• Change the SECOND CODE NO. according to
“
Table 5
” depending on the amount of dirt or dust in
the room
.
(SECOND CODE NO. is factory set to
“
01
”
for air filter contamination-light.)
Table5
10-4 When implementing group control
• When using as a pair unit, you may control up to 16 unit with the remote controller.
• In this case, all the indoor units in the group will operate in accordance with the group control remote con-
troller.
• Select a remote controller which matches as many of the functions (swing flap, etc) in the group as possi-
ble.
Wiring Method
(See 9. ELECTRIC WIRING WORK on page 15.)
(1)
Remove the control box lid.
(2) Cross-wire the remote control terminal block (P
1
P
2
) inside the control box. (There is no polarity.)
(Refer to Fig. 27 on page 14 and Table 4 on page 15)
Setting
Spacing time of display air filter
sign (long life type)
Mode No.
FIRST CODE
NO.
SECOND
CODE NO.
Air filter contamination-
light
Approx. 2500 hrs
10 (20)
0
01
Air filter contamination-
heavy
Approx. 1250 hrs
02
Outdoor unit 1
Indoor unit 1
Group control remote controller
Indoor unit 2
Indoor unit 3
Outdoor unit 2
Outdoor unit 3