SiUS091628EA
Troubleshooting
Service Diagnosis
78
4.13 Mismatching of Indoor Unit and Outdoor Unit
Error Code
UA
Error Decision
Conditions
Improper combination of indoor and outdoor units
Supposed
Causes
Defective indoor unit PCB
Indoor-outdoor unit transmission wiring error
Defective optional unit(s) wirings
Improper power supply wiring of indoor unit
Improper wiring of connecting wires between indoor/outdoor units
Troubleshooting
Connect the wirings correctly.
Replace the indoor unit PCB
(control PCB).
Normal
Connect the wirings correctly.
Check the power supply system
inside the indoor unit.
Could be incorrect wiring.
Check again.
YES
YES
NO
NO
Connect the indoor/outdoor
units correctly.
YES
YES
YES
YES
NO
NO
NO
Blink
(R24372)
Is the combination
of indoor/outdoor
units correct?
Do the service
monitors of all the
indoor units blink?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Connect the wirings correctly.
NO
Is the optional
units power supply
connected from the
indoor unit terminal
block No.1 and
No.2?
Does the system conduct
normal operation?
Are the wirings
between indoor unit and
outdoor unit correctly
connected?
Turn off the power supply.
Then, turn on the power
supply to restart the system.
Continuously
ON or OFF
Is the voltage
between No.1 and
No.2 on the indoor
unit terminal block
208 - 230
VAC?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU
Страница 12: ...SiUS091628EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiUS091628EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 120: ...Check SiUS091628EA 109 Service Diagnosis 15 18 class R20701 1 2 3 4 Multimeter...
Страница 122: ...Check SiUS091628EA 111 Service Diagnosis 15 18 class R20704 W V U DC_P1 DC_N1...