6 Installation

Installer and user reference guide

13

FFA25~60A2VEB(9)
Split system air conditioners
4P550955-4 – 2018.08

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centers.  You  can  attach
the paper pattern to the unit.

a

c

b

d

a

Centre of the unit

b

Centre of the ceiling opening

c

Paper pattern for installation (upper part of the packing)

d

Screws (accessories)

Ceiling opening and unit

:

▪ Make sure the ceiling opening is within the following limits:

Minimum

: 585 mm to be able to fit the unit.

Maximum

:  660  mm  in  case  of  installation  with  BYFQ60B  and

595  mm  in  case  of  installation  with  BYFQ60C  ensure  enough
overlapping  between  the  decoration  panel  and  the  suspended
ceiling.  If  the  ceiling  opening  is  larger,  add  extra  ceiling
material.

▪ Make  sure  the  unit  and  its  hanger  brackets  (suspension)  are

centered within the ceiling opening.

(mm)

c

d

A

B

A B

533

350

575

c d

533

575

b

a

A

585~660 mm:

 In case of installation with BYFQ60B

585~595  mm:

 In case of installation with BYFQ60C

B

700 mm:

 In case of installation with BYFQ60B

620  mm:

 In case of installation with BYFQ60C

a

Drain piping

b

Refrigerant piping

c

Hanger bracket pitch (suspension)

d

Unit

Then

If A

B

C

A

C

B

BYFQ60B

≥585 mm

5 mm

57.5 mm

≤660 mm

42.5 mm

20 mm

BYFQ60C

≥585 mm

5 mm

17.5 mm

≤595 mm

10 mm

12.5 mm

A

Ceiling opening

B

Distance between the unit and the ceiling opening

C

Overlap between the decoration panel and the suspended
ceiling

Level

. Make sure the unit is level at all 4 corners using a level or a

water-filled vinyl tube.

c

b

b

a

a

Level

b

Vinyl tube

c

Water level

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

6.2.3

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤630~675  mm

(depending on the decoration panel used) perpendicular to the
unit.

A

B

≤300

0~75

1000~1500

(mm)

b

a

b

c

a

d

d

Содержание FFA50A2VEB9

Страница 1: ...ser reference guide Split system air conditioners English Installer and user reference guide Split system air conditioners FFA25A2VEB FFA35A2VEB FFA50A2VEB FFA60A2VEB FFA25A2VEB9 FFA35A2VEB9 FFA50A2VE...

Страница 2: ...electrical wiring 17 6 4 4 Specifications of standard wiring components 17 6 4 5 To connect the electrical wiring on the indoor unit 17 7 Configuration 18 7 1 Field settings 18 8 Commissioning 19 8 1...

Страница 3: ...ildren aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning us...

Страница 4: ...ed Do NOT block any ventilation openings Make sure the unit is level Do NOT install the unit in the following places In potentially explosive atmospheres In places where there is machinery that emits...

Страница 5: ...5 92 6 6 27 6 3 0 76 6 6 6 371 3 2 6 48 6 8 29 3 3 2 87 2 6 8 394 3 4 7 32 7 0 31 0 3 4 98 4 7 0 417 3 6 8 20 7 2 32 8 3 6 110 7 2 441 3 8 9 14 7 4 34 7 3 8 123 7 4 466 4 0 10 1 7 6 36 6 4 0 136 7 6 4...

Страница 6: ...n Open refrigerant cylinders slowly Charge the refrigerant in liquid form Adding it in gas form may prevent normal operation CAUTION When the refrigerant charging procedure is done or when pausing clo...

Страница 7: ...head and make proper tightening impossible Over tightening the terminal screws may break them WARNING After finishing the electrical work confirm that each electrical component and terminal inside th...

Страница 8: ...ter describes what you have to do after the box with the indoor unit is delivered on site Keep the following in mind At delivery the unit MUST be checked for damage Any damage MUST be reported immedia...

Страница 9: ...5 46 C DB 9 21 C DB 10 15 C WB 18 37 C DB 12 28 C WB 10 27 C DB RXS25 60 10 46 C DB 15 24 C DB 16 18 C WB 18 32 C DB 10 30 C DB Outdoor units Cooling Heating 2MXS50 10 46 C DB 15 24 C DB 16 18 C WB 1...

Страница 10: ...ance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial and light industrial en...

Страница 11: ...ce to the floor see below C 295 mm In case of installation with BYFQ60B 300 mm In case of installation with BYFQ60C a Indoor unit b Lighting the figure shows ceiling mounted lighting but recessed ligh...

Страница 12: ...or installation INFORMATION This chapter only describes installation instructions specific to the indoor unit For the other instructions see The installation manual of the outdoor unit The installatio...

Страница 13: ...5 mm 595 mm 10 mm 12 5 mm A Ceiling opening B Distance between the unit and the ceiling opening C Overlap between the decoration panel and the suspended ceiling Level Make sure the unit is level at a...

Страница 14: ...6 5 2 c e 4 b a d b a d c 3 1 2 6 1 a Drain pipe connection attached to the unit b Drain hose accessory c Metal clamp accessory d Large sealing pad accessory e Insulation piece drain pipe accessory f...

Страница 15: ...refrigerant to be used Only use installation tools e g manifold gauge set that are exclusively used for R32 or R410A installations to withstand the pressure and to prevent foreign materials e g minera...

Страница 16: ...tions Insulation Insulate the refrigerant piping on the indoor unit as follows A B a d c e f b b a d c e f b b 2 4 3 g 1 2 3 4 g A B 1 A Gas piping B Liquid piping a Insulation material field supply b...

Страница 17: ...30 V User interface cable Vinyl cords with 0 75 to 1 25 mm sheath or cables 2 core wires Maximum 500 m 6 4 5 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delive...

Страница 18: ...t they correspond with the actual installation setup and with the needs of the user Ceiling height Air flow direction Air volume when thermostat control is OFF Time to clean air filter Setting Ceiling...

Страница 19: ...power consumption NOTICE Before starting up the system the unit MUST be energised for at least 6 hours The crankcase heater needs to heat up the compressor oil to avoid oil shortage and compressor bre...

Страница 20: ...it first The backlight is lit for 30 seconds when you press a button 1 Perform introductory steps Action 1 Open the liquid stop valve A and gas stop valve B by removing the stem cap and turning counte...

Страница 21: ...hase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires U4 or UF The inter unit branch wiring is not correct UA The...

Страница 22: ...ESS H P LED V L PILOT LAMP LIGHT EMITTING DIODE HAP LIGHT EMITTING DIODE SERVICE MONITOR GREEN HIGH VOLTAGE HIGH VOLTAGE IES INTELLIGENT EYE SENSOR IPM INTELLIGENT POWER MODULE K R KCR KFR KHuR K M MA...

Страница 23: ...ce see the operation manual of the installed user interface 13 Before operation WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been...

Страница 24: ...n It may take longer to reach the set temperature for general heating operation than for cooling operation The following operation is performed in order to prevent the heating capacity from dropping o...

Страница 25: ...lades while the swing flap is in operation Fingers may become caught or the unit may break down NOTICE The movable limit of the flap is changeable Contact your dealer for details only for double flow...

Страница 26: ...result in burnout of these components 16 1 Cleaning the air filter suction grille air outlet and outside panels 16 1 1 To clean the air filter When to clean the air filter Rule of thumb Clean every 6...

Страница 27: ...in order to dry the interior of the units Refer to 14 2 2 About cooling heating fan only and automatic operation on page 24 for details on fan only operation Turn off the power The user interface dis...

Страница 28: ...face and switches 25 000 hours Drain pan 8 years Expansion valve 20 000 hours Solenoid valve 20 000 hours The table assumes the following conditions of use Normal use without frequent starting and sto...

Страница 29: ...N OFF button on the user interface is pressed If the operation lamp lights the system is in normal condition To prevent overloading of the compressor motor the air conditioner starts 5 minutes after i...

Страница 30: ...s is to prevent refrigerant from remaining in the compressor The unit will stop after 5 to 10 minutes 18 Relocation Contact your dealer for removing and reinstalling the total unit Moving units requir...

Страница 31: ......

Страница 32: ...4P550955 4 2018 08 Copyright 2017 Daikin...

Отзывы: