Specification

ED41-016B

6

FDYB-KA Series

Notes:

1.

1 Nominal capacities are based on the following conditions.

2. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
3.

2 Air Fiow Rate is shown at 220V (380V)–240V (415V).

4.

3 Each value for indoor unit shows the specification per one unit.

5. In case of drain piping for outdoor unit, drain piping kit (option) is needed.

Model

Indoor Unit

FDYB50KAVE×4

FDYB71KAVE×3

FDYB60KAVE×4

Outdoor Unit

RY200KUY1

RY200KUY1

RY250KUY1

1  Cooling Capacity  (1)/(2)/(3)

kW

22.5 / 22.2 / 22.0

27.1 / 26.6 / 26.3

Btu/h

76,800 / 75,800 / 75,100

92,500 / 90,800 / 89,800

kcal/h

19,400 / 19,100 / 18,900

23,300 / 22,900 / 22,600

1  Heating Capacity (1)/(2)/(3)

kW

22.6

 

 / 22.7 / 22.6

28.3 / 28.4 / 28.3

Btu/h

77,200

 

 / 77,500 / 77,200

96,600 / 97,000 / 96,600

kcal/h

19,400

 

 / 19,500 / 19,400

24,300

 

 / 24,400 / 24,300

Indoor Unit

       ∗

3

FDYB50KAVE

FDYB71KAVE

FDYB60KAVE

Dimensions

H×W×D

mm

260×900×580

260×1,300×580

Coil

Type

Cross Fin Coil (Waffle Louver Fins and Hi–XA Tubes)

Row×Stages×Fin Pitch

3×10×1.75

Face Area

0.189

0.231

Fan

Model

Type

Sirocco Fan

Motor Output

W

45

65

Air Flow Rate

m³/min

(H) 13  (L) 11

(H) 18  (L) 15

Mass (Weight)

kg

23

31

Piping Connections

Liquid

mm

φ

6.4 (Flare)

φ

9.5 (Flare)

φ

6.4 (Flare)

Gas

mm

φ

15.9 (Flare)

Drain

in.

3/4 B

Remote Controller

Wired

BRC1C61

Wireless

BRC4C62

Outdoor Unit

RY200KUY1

RY60GVA

RY71FUVAL

Color

Ivory

Dimensions

H×W×D

mm

1,220×1,280×690

1,440×1,280×690

Coil

Type

Cross Fin Coil (FL Fins and Hi–XA Tubes)

Row×Stages×Fin Pitch

2×40×2.0

2×50×2.0

Face Area

1.57

1.97

Comp.

Model

JT236D–P1YE

JT335D–P1YE

Type

Hermetically Sealed Scroll Type

Motor Output

kW

5.5

9.0

Fan

                   ∗

2

Model

P52H11SM

Type

Propeller

Motor Output

W

230+190

Air Flow Rate (C / H)

m³/min

150–154 / 138–142

175–179 / 161–165

Mass (Weight)

kg

180

206

Piping Connections

Liquid

mm

φ

12.7 (Flare)

φ

15.9 (Flare)

Gas

mm

φ

25.4 (Flange)

φ

28.6 (Flange)

Drain

mm

Safety Devices

Thermal protector for compressor. Outdoor fan motor and indoor fan motor.

High pressure Switch. Low pressure Switch. Over Current relay (Compressor). Reverse phase protector. Fuse. 

Capacity Step

%

100 – 0

Refrigerant Control

Capillary Tube

Ref. Piping

Standard Length

m

Max. Length

m

50 (Equivalent Length 70m)

Max. Height Difference

m

30

Refrigerant

Model

R22

Charge

kg

4.0 (Factory Charge for 5m)

5.5 (Factory Charge for 5m)

Ref. Oil

Model

SUNISO 4GSDID–K

Charge

L

3.0

Drawing No.

4D032950A

Mark

Cooling

Heating

Piping length

Hz–Volts

Standard

(1)

Indoor : 

27°C(81°F)DB, 19.5°C(67°F)WB

Indoor : 

21°C(70°F)DB, 15°C(59°F)WB

5m 

(Horizontal)

50Hz–380V

Outdoor :  35°C(95°F)DB, 24°C(75°F)WB

Outdoor :  7°C(45°F)DB, 6°C(43°F)WB

(2)

Indoor : 

27°C(81°F)DB, 19.0°C(66°F)WB

Indoor : 

20°C(68°F)DB, 15°C(59°F)WB

5m 

(Horizontal)

50Hz–380V

Outdoor :  35°C(95°F)DB, 24°C(75°F)WB

Outdoor :  7°C(45°F)DB, 6°C(43°F)WB

(3)

Indoor : 

27°C(81°F)DB, 19.0°C(66°F)WB

Indoor : 

20°C(68°F)DB, 15°C(59°F)WB

7.5m 

(Horizontal)

50Hz–415V

AS 3823

Outdoor :  35°C(95°F)DB, 24°C(75°F)WB

Outdoor :  7°C(45°F)DB, 6°C(43°F)WB

Содержание FDYB-KA Series

Страница 1: ...Packaged Air Conditioners Duct Connection Type Low Static Pressure Application FDYB KA Series Heat Pump ED 41 016B...

Страница 2: ...pace 17 6 Piping Diagrams 20 6 1 50Hz 20 6 2 60Hz 24 7 Wiring Diagrams 27 7 1 Indoor Units 27 7 2 Outdoor Units 28 8 Capacity Table 35 8 1 50Hz 35 8 2 60Hz 38 8 3 Change in Capacity Reference 41 9 Ope...

Страница 3: ...0KAVE RY60GVAL FDYB71KAVE RY71FUVAL 3 220V 60Hz FDYB50KAVE 4 RY200KUTAL FDYB71KAVE 3 RY200KUTAL FDYB60KAVE 4 RY250KUTAL 3 380V 60Hz FDYB50KAVE 4 RY200KUYAL FDYB71KAVE 3 RY200KUYAL FDYB60KAVE 4 RY250KU...

Страница 4: ...Appearance 2 1 External Appearance 2 1 1 Indoor Units 2 1 2 Remote Controller 2 1 3 Outdoor Units FDYB35KAVE FDYB50KAVE FDYB60KAVE FDYB71KAVE Wired Wireless BRC1C61 BRC4C62 Signal Receiving Unit Sepa...

Страница 5: ...trol by 2 remote controllers Group Control by 1 remote controller External command control Central remote control Interlock control with HRV PE fin Adjustable external static pressure 1 Air conditione...

Страница 6: ...l Waffle Louver Fins and Hi XA Tubes Row Stages Fin Pitch 2 22 2 0 2 28 2 0 2 36 2 0 Face Area m 0 372 0 46 0 50 0 653 Comp Model V1 RC53V1TNRT RC70AV1TRT NH41VMDT JT95BC V1 Y1 JT95BC YE Type Hermetic...

Страница 7: ...r Ivory Dimensions H W D mm 1 220 1 280 690 1 440 1 280 690 Coil Type Cross Fin Coil FL Fins and Hi XA Tubes Row Stages Fin Pitch 2 40 2 0 2 50 2 0 Face Area m 1 57 1 97 Comp Model JT236D P1YE JT335D...

Страница 8: ...Row Stages Fin Pitch 2 28 2 0 2 36 2 0 Face Area m 0 372 0 465 0 653 Comp Model RC60VHNRT RC75VHTR2T H23A38QABCA Type Hermetically Sealed Rotary Type Hermetically Sealed Type No of cylinders 2 Motor O...

Страница 9: ...lor Ivory Dimensions H W D mm 1 220 1 280 690 1 440 1 280 690 Coil Type Cross Fin Coil Waffle Louver Fins and Hi XA Tubes Row Stages Fin Pitch 2 40 2 0 2 50 2 0 Face Area m 1 57 1 97 Comp Model TAL JT...

Страница 10: ...ED41 016B Dimensions FDYB KA Series 9 5 Dimensions 5 1 Indoor Units FDYB35KA Unit mm C 3D024200B...

Страница 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...

Страница 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...

Страница 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...

Страница 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...

Страница 15: ...Dimensions ED41 016B 14 FDYB KA Series RY60GA RY71KU Unit mm 3D004852A Unit mm C 3D014835 3 9 6...

Страница 16: ...ED41 016B Dimensions FDYB KA Series 15 RY71FU RY200KU Unit mm 3 9 6 C 3D001674A Unit mm C 3D029265...

Страница 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...

Страница 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...

Страница 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...

Страница 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...

Страница 21: ...iagrams 6 1 50Hz RY35FV1A RY50GAV1A Indoor heat exchanger Indoor unit Filter Field piping f 6 4 C1220T 0 Field piping f 12 7 C1220T 0 C 3D002723 Indoor heat exchanger Indoor unit Filter Field piping f...

Страница 22: ...ED41 016B Piping Diagrams FDYB KA Series 21 RY60GAV1A RY71KUV1 Y1 C 3D028562 Indoor heat exchanger Indoor unit Filter Field piping f 6 4 C1220T 0 Field piping f 15 9 C1220T 0 3D014830B...

Страница 23: ...Piping Diagrams ED41 016B 22 FDYB KA Series RY200KUY1 Double Twin RY200KUY1 Triple C 3D029824 C 3D029825...

Страница 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...

Страница 25: ...2 60Hz RY50GVAL RY60GVAL C 3D008108A Indoor heat exchanger Indoor unit Filter Field piping f 6 4 C1220T 0 Field piping f 15 9 C1220T 0 C 3D008109A Indoor heat exchanger Indoor unit Filter Field pipin...

Страница 26: ...ED41 016B Piping Diagrams FDYB KA Series 25 RY71FUVAL RY200KUTAL YAL Double Twin 3D005825 3D030159...

Страница 27: ...Piping Diagrams ED41 016B 26 FDYB KA Series RY200KUTAL YAL Triple RY250KUTAL YAL Double Twin 3D030160 3D030164...

Страница 28: ...ED41 016B Wiring Diagrams FDYB KA Series 27 7 Wiring Diagrams 7 1 Indoor Units FDYB35KAVE FDYB50KAVE FDYB60KAVE FDYB71KAVE 3D024173D...

Страница 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...

Страница 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...

Страница 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...

Страница 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...

Страница 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...

Страница 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...

Страница 35: ...Wiring Diagrams ED41 016B 34 FDYB KA Series 7 2 3 50Hz 60Hz RY200KUY1 YAL RY250KUY1 YAL 3D028900A 3D028901A...

Страница 36: ...ED41 016B Capacity Table FDYB KA Series 35 8 Capacity Table 8 1 50Hz FDYB35KAVE RY35FV1A FDYB50KAVE RY50GAV1A 3D024735A 3D024736A...

Страница 37: ...Capacity Table ED41 016B 36 FDYB KA Series FDYB60KAVE RY60GAV1A FDYB71KAVE RY71KUY1 FDYB71KAVE RY71KUV1 3D024737A 3D024738A...

Страница 38: ...ED41 016B Capacity Table FDYB KA Series 37 FDYB50KAVE 4 RY200KUY1 FDYB71KAVE 3 RY200KUY1 FDYB60KAVE 4 RY250KUY1 3D029856A 3D029853A...

Страница 39: ...Capacity Table ED41 016B 38 FDYB KA Series 8 2 60Hz FDYB50KAVE RY50GVAL FDYB60KAVE RY60GVAL 3D024739A 3D024740A...

Страница 40: ...ED41 016B Capacity Table FDYB KA Series 39 FDYB71KAVE RY71FUVAL FDYB50KAVE 4 RY200KUTAL FDYB71KAVE 3 RY200KUTAL FDYB50KAVE 4 RY200KUYAL FDYB71KAVE 3 RY200KUYAL 3D024741A 3D029857A...

Страница 41: ...Capacity Table ED41 016B 40 FDYB KA Series FDYB60KAVE 4 RY250KUTAL FDYB60KAVE 4 RY250KUYAL 3D029855A...

Страница 42: ...y line Correction factor for cooling capacity 2 The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit 3 You cannot extend the refrigerant pi...

Страница 43: ...Operation Limit ED41 016B 42 FDYB KA Series 9 Operation Limit 9 1 50Hz 35 71 RY35FV1A RY50GAV1A RY60GAV1A RY71KUV1 RY71KUY1 DU427 963A...

Страница 44: ...ED41 016B Operation Limit FDYB KA Series 43 9 2 60Hz 50 71 RY50GVAL RY60GVAL RY71FUVAL 3D006202A 3D006675...

Страница 45: ...Operation Limit ED41 016B 44 FDYB KA Series 9 3 50Hz 60Hz 200 250 RY200KUY1 TAL YAL RY250KUY1 TAL YAL 3D029783...

Страница 46: ...220V Y1 380V V1 240V Y1 415V Cooling Heating Cooling Heating Cooling Heating RY35F 47 48 48 49 RY50G A 49 49 50 52 51 51 RY60G A 54 54 56 56 53 51 RY71KU FU 48 50 49 51 53 55 RY200KU 60 62 61 63 60 62...

Страница 47: ...Octave band sound pressure level dB 0dB 0 0002m bar 4D014428 Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002m bar 4D014429 Octave band center frequency Hz Octave band s...

Страница 48: ...Hz Octave band sound pressure level dB 0dB 0 0002m bar 3D008113 Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002m bar 4D007382 Octave band center frequency Hz Octave ban...

Страница 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...

Страница 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...

Страница 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...

Страница 52: ...0 19 1 3 1 2 0 065 3 0 5 3 FDYB50KAVE 4 RY200KUY1 20 4 22 1 30 87 92 95 12 6 12 4 13 0 0 23 0 19 1 3 1 2 0 045 4 0 4 4 FDYB60KAVE 4 RY250KUY1 26 0 28 5 40 128 135 140 16 3 15 7 17 2 0 23 0 19 1 3 1 2...

Страница 53: ...BRC1C61 Optional Accessory Kit Name FDYB35KAVE FDYB50KAVE FDYB60KAVE FDYB71KAVE Remote Controller Wired BRC1C61 Wireless BRC4C62 Central Remote Controller 1 DCS302B61 Unified ON OFF Controller 1 DCS30...

Страница 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...

Страница 55: ...field wiring and components must be provided by a licensed electrician 7 Unit shall be grounded in compliance with the applicable local and national codes 8 Wiring shown are general points of connecti...

Страница 56: ...hat shown on the name plate Are wiring and piping correct Is the unit safely grounded Is wiring size according to specifications Is something blocking the air outlet or inlet of either the indoor or o...

Страница 57: ...ept Ambient air of the indoor unit is not so dusty Drain piping may be clogged with dust and may result in water leakage and property damage When obliged to install the indoor unit in a dusty place in...

Страница 58: ...wn in the drawing when connecting or disconnecting pipes to from the unit Fig 7 Refer to Table 1 for the dimensions of flare nut spaces When connecting the flare nut coat the flare both inside and out...

Страница 59: ...3 WRONG CORRECT Fig 10 Rig drain piping Keep piping as short as possible and slope it downwards so that air may not remained trapped inside the pipe WARNING Rig the drain pipe as shown below and take...

Страница 60: ...wire for the remote controller or run wires through a wall or conduit so that the user cannot come in contact with them 4 Run transmission wiring between the indoor and outdoor units through a conduit...

Страница 61: ...ons and fix the wires so that outside forces are not applied to the terminals Apply clamp to wiring so as not to slide even if wiring is pulled Surely fasen wiring by clamp Power supply terminal board...

Страница 62: ...3PN00281 18T 9 For the wiring of outdoor units In case of 71 model refer to the installation manual attached to the outdoor unit In case of another model refer to the section entitled OUTDOOR UNIT INS...

Страница 63: ...del BRC1B62 MAIN SUB CHANGEOVER 1 Insert a screwdriver into the recess between the upper and lower part of remote controller and working from the 2 positions pry off the upper part The remote controll...

Страница 64: ...TING INSTALLATION SITE Select an installation site where the following conditions are satisfied and that meets with your customer s approval Places which are well ventilated Safe places which can with...

Страница 65: ...m No pressure increase for 1 minute 2 Charge Nitrogen N2 3 Check for leaks by applying soap water to pipe connections 4 Discharge Nitrogen 5 Conduct air purge again and check vacuum 6 Open valves and...

Страница 66: ...12 Nakazaki Nishi 2 chome Kita ku Osaka 530 8323 Japan Tokyo Office Shinjuku Sumitomo Bldg 6 1 Nishi Shinjuku 2 chome Shinjuku ku Tokyo 163 0235 Japan Internet http www daikin com global ED41 016B Thi...

Отзывы: