SiSG121917E
Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
150
Reference
Reference
7.9 Compressor Lock
Error Code
E6
Outdoor Unit LED
Display
A
j
1
h
2
i
3
i
4
h
5
h
Method of Error
Detection
A compressor lock is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
Judging from the current waveform generated when high-frequency voltage is applied to the
compressor.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 5 minutes without any other error
Supposed
Causes
Defective outdoor unit PCB
Defective compressor
Defective electronic expansion valve
Troubleshooting
Check No.12
Refer to P.172
Check No.15
Refer to P.173
Turn off the power. Disconnect the
harnesses U,
V
, and W.
(R21163)
Caution
NO
YES
YES
NO
NO
YES
Check No.15
Check with the inverter analyzer.
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
∗
Inverter analyzer:
RSUK0917C
Replace the compressor.
Replace the compressor.
Check the electronic
expansion valve coil.
Replace it as required.
Go to
Check No. 12
.
Any LED off?
Emergency
stop without compressor
running?
System shut
down after errors repeated
several times?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...