Part 6 Service Diagnosis
6. Troubleshooting for MSP Duct Type Indoor Unit
6.1 Indoor Unit PCB Abnormality
Error Code
A1
Method of Error
Detection
The system checks the data from EEPROM.
Error Decision
Conditions
When the data from the EEPROM is not received correctly
EEPROM (Electrically Erasable Programmable Read Only Memory): A memory chip that holds
its content without power. It can be erased, either within the computer or externally and usually
requires more voltage for erasure than the 5 volts used in logic circuits. It functions
like non-volatile RAM, but writing to EEPROM is slower than writing to RAM.
Supposed
Causes
Defective indoor unit PCB
External factor (noise etc.)
Troubleshooting
Caution
Be s
u
re to t
u
rn off the po
w
er s
w
itch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
(R22247)
N
ormal?
T
u
rn off the po
w
er. Then, t
u
rn on
the po
w
er to restart the system.
N
O
YES
External factor other than malf
u
nction
(for example, noise etc.)
Replace the indoor
u
nit PCB
(control PCB).
Содержание FDMR50TVMG
Страница 185: ...SiSG121917E Check Part 6 Service Diagnosis 180 50 65 80 class 90 class V U DC DC R22378 W R21130 W V U DCP2 DCM2 ...
Страница 212: ...Piping Diagrams SiSG121917E 207 Part 8 Appendix MKS65TVMG MKB65TVMG MKS80TVMG 3D103941A 3D103942A ...
Страница 213: ...SiSG121917E Piping Diagrams Part 8 Appendix 208 MKS90TVMG 3D104086 ...
Страница 223: ...SiSG121917E Operation Limit Part 8 Appendix 218 3 Operation Limit MKS50 65 80 90TVMG MKB50 65TVMG 4D078793B ...