Control Specification
SiUS071735EB
37
Functions and Control
2.6 Freeze-up Protection Control
Outline
During cooling operation, the signal sent from the indoor unit determines the frequency upper limit
and prevents the indoor heat exchanger from freezing.
Details
When the freeze-up protection control starts, the compressor stops, the airflow rate is fixed to L tap,
and the drain pump turns ON. Conditions for starting and ending are as below.
Starting conditions
The freeze-up protection control starts when any of the following conditions is satisfied.
The indoor heat exchanger temperature remains at
A
or lower for 1 minute.
The accumulated time that the indoor heat exchanger temperature remains at
B
or lower
reaches 40 minutes.
Accumulated timer clearing condition
The indoor heat exchanger temperature remains at
C
or higher for 20 minutes.
Ending condition
The indoor heat exchanger temperature remains at
D
or higher for 10 minutes.
(°C)
(°F)
A
–5
23.0
B
–1
30.2
C
4
39.2
D
7
44.6
D
A
B
C
Indoor heat
exchanger
temperature
The control starts.
The control starts.
The control ends
and the accumulated timer is cleared.
The accumulated timer is cleared.
Содержание FDMQ09RVJU
Страница 12: ...SiUS071735EB 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiUS071735EB 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 125: ...SiUS071735EB Check Service Diagnosis 114 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 127: ...SiUS071735EB Check Service Diagnosis 116 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 143: ...SiUS071735EB Piping Diagrams Appendix 132 1 Piping Diagrams 1 1 Indoor Unit FDMQ09 12 15 18 24RVJU C 4D112974A ...