background image

5 Configuration

Installation and operation manual

8

FCAHG71~140HVEB

Split system air conditioners

4P535639-1B – 2019.01

4.3.1

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

4-core cable

1.5 mm

2

~2.5 mm

2

 and

applicable for 220~240 V

H05RN-F (60245 IEC 57)

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

Maximum 500 m

H03VV-F (60227 IEC 52)

4.3.2

To connect the electrical wiring on the
indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For instructions on how to connect the decoration panel

and the sensor kit, see the installation manual delivered
with the panel or the kit.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

5

Reattach the service cover.

NOTICE

When  closing  the  service  cover,  make  sure  that  the
tightening torque for screws is ≤1.5N•m.

▪ Following  installation  is  for  pair  type  or  multi-system.  For  more

installation options, see the Installer reference guide of the indoor
unit.

1~ 50 Hz

220-240 V

b

a

e1

c

d

a

Interconnection cable

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e1

Main user interface

a

(mm)

e

e

b

c

10~15

70~90

10~20

d

c

b

10~15

d

70~90

7

a

Service cover (with wiring diagram on the back)

b

Opening for cables

c

Connection of interconnection cable (including earth)

d

Cable tie

e

Connection of user interface cable

5

Configuration

5.1

Field settings

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Ceiling height

▪ Design decoration panel (if applicable)

▪ Air flow direction

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

Setting: Ceiling height

This  setting  must  correspond  with  the  actual  distance  to  the  floor,
capacity class and air flow directions.

▪ For 3-way and 4-way air flows (which require an optional blocking

pad  kit),  see  the  installation  manual  of  the  optional  blocking  pad
kit.

▪ For all-round air flow, use the table below.

Содержание FCAHG71HVEB

Страница 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAHG71HVEB FCAHG100HVEB FCAHG125HVEB FCAHG140HVEB...

Страница 2: ...abljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytus standartus...

Страница 3: ...culation airflow 14 12 5 1 To start the active circulation airflow 14 13 Maintenance and service 15 13 1 Precautions for maintenance and service 15 13 2 Cleaning the air filter suction grille air outl...

Страница 4: ...n 70 dBA CAUTION Appliance not accessible to the general public install it in a secured area protected from easy access This unit both indoor and outdoor is suitable for installation in a commercial a...

Страница 5: ...4 a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine...

Страница 6: ...accessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condens...

Страница 7: ...are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion WARNING FLAMMABLE MATERIAL The R32 refrigerant if applicable in this unit is mildly...

Страница 8: ...h the numbers on the outdoor unit and connect the earth wire and fix the cable with a cable tie 4 Divide the small sealing accessory and wrap it around the cables to prevent water from entering the un...

Страница 9: ...ification is displayed on the user interface When using a wireless user interface you must also set the address see the installation manual of the user interface If you want an interval of air contami...

Страница 10: ...amaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves...

Страница 11: ...cked E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The a...

Страница 12: ...N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC Thermistor PTC Q Insulated gate bipolar trans...

Страница 13: ...12 Operation 12 1 Operation range Use the system in the following temperature and humidity ranges for safe and effective operation In combination with R410A outdoor units Outdoor units Cooling Heating...

Страница 14: ...flow units For the following conditions a micro computer controls the air flow direction which may be different from the display Cooling Heating When the room temperature is lower than the set tempera...

Страница 15: ...f If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth CAUTION Before accessing terminal devices make sure to...

Страница 16: ...sible consequence Discoloration and deformation Do NOT scrub firmly when washing the blade with water Possible consequence The surface sealing peels off Clean with a soft cloth If it is difficult to r...

Страница 17: ...hich the refrigerant leaked has been repaired 14 Troubleshooting If one of the following malfunctions occur take the measures shown below and contact your dealer WARNING Stop operation and shut off th...

Страница 18: ......

Страница 19: ......

Страница 20: ...4P535639 1B 2019 01 Copyright 2018 Daikin...

Отзывы: