English
8
(6) Hook the indoor unit onto the installation panel. (Refer to Fig. 9)
•
Placing buffering material between the wall and the indoor unit at this time will make work easier.
For right, bottom-right, and back-right piping
•
Pass the drain hose and the refrigerant piping to the wall.
(7) Pass wiring the units, ground wiring, and remote controller wiring through the wiring guide in
through the back of the indoor unit and to the front.
(8) Connect the piping. (See “5.REFRIGERANT PIPING WORK” and Fig. 10)
•
To avoid the influence of noise from the power supply line on the remote controller wiring, this wiring
must be kept as far as possible from wiring the units/ground wirings. As shown in the Fig.10, keep the
wiring the units and the ground wiring together. Route remote controller wiring maintaining a good dis-
tance from the wiring the units/ground wirings (that is, on the other side of the wiring the units/ground
wirings). Then, fix them securely on the refrigerant pipe.
•
Seal the piping through-hole with putty corking material.
(9) Push on both bottom edges of the indoor unit using both hands and hook the tab on the back of
the indoor unit onto the installation panel (1). (Refer to Fig. 9)
•
At this time remove the buffering material placed in step (6).
Refrigerant pipe
Be sure to pass all wires through
the wiring guide.
Tab
(There are 2 places.)
Wiring (locally procured)
Wiring the units, Ground wiring, Remote controller wiring
Wall
Installation panel
(accessory) (1)
Front panel
Front grill
Service lid
Place buffering material
Hook the indoor unit hook onto the installation panel (1).
Fig. 9
Secure with
vinyl tape.
Wrap the insulating tape overlapping at least half the width with
each wrap.
Wrap the insulating tape all the way to the L-shaped bend.
Seal with putty corking
material.
Drain hose
Wiring
Fig. 10
Refrigerant piping
A
A
arrow view
Wiring the units and
ground wiring
Refrigerant piping
Remote controller wiring
01_EN_3P083811-3T.fm Page 8 Friday, September 3, 2004 10:17 AM