EWWQ090G ÷ EWWQ720L - R410A - Water-cooled scroll chillers
EWLQ090G ÷ EWLQ720L - R410A - Condenser less
EWHQ100G ÷ EWHQ400G - R410A - Heat pump scroll chillers
EWAQ-G 075
- R410A - Air-cooled scroll chillers
EWAQ-
- R410A - Air-cooled scroll chillers
EWYQ-
- R410A - Air-cooled scroll heat pumps
Air and Water cooled scroll chillers & heat pump
Operation
Manual
Operation Manual
24
EWWQ - EWLQ - EWHQ
EWAQ - EWYQ
Air or Water cooled scroll chiller &
heat pump
D-EOMHW00107-15EN
In case of BSP update the BSP led will stop in off. If this happen the update process has to be
repeated once more. If the BSP led will stop in yellow color the process is completed and the
controller restarted.
After the controller is restarted the BSP led will blink green during the boot up and then it will
remain solid green to indicate normal operations. It’s now possible to restore the previous settings
if available and restart the unit.
3.8 Optional Remote User Interface
As an option an external Remote HMI can be connected on the UC. The Remote HMI offers the
same features as the inbuilt display plus the alarm indication done with a light emitting diode
located below the bell button.
The Remote interface can be ordered with the unit and shipped loose as a field installed option. It
can also be ordered anytime after chiller shipment, mounted and wired on the job site as explained
in the following.
The remote panel is powered directly from the UC. No additional power supply is required.
All views, data and setpoint adjustments available on the UC HMIs are available on the remote
panel. Navigation is identical to the UC as described in this manual.