D-EIMWC01405-18EN- 14/32
2.9
Temperature limits and water flow
EWWD(H) DZ units are designed to operate with an evaporate outlet water temperature between 4°C and +20°C and a
condenser outlet water temperature between 20°C and 50°C. However, the minimum temperature difference between the
evaporator outlet water temperature and the condenser inlet water temperature must not be less than 15° C. Always check
the exact operating point with the selection software. Some simultaneous operating conditions (high evaporator inlet water
temperature and high condenser inlet water temperature) may be inhibited. The maximum permissible water temperature
in the evaporator with the machine off is 50° C. Higher temperatures could cause the safety valves on the evaporator
sleeve to open. Water flow rate in the condenser and evaporator under the rated value indicated in the unit selection point
can cause freezing problems, scale and poor control. Water flow rate in the condenser and evaporator higher than the
rated value indicated in the unit selection point results in an unacceptable pressure drop and excessive erosion of the
pipes and vibrations that can cause breakage.
EWWD(H)-DZ DRY COOLER VERSION
Dry cooler version Model
EWWD320DZXSA1
EWWH230DZXSA1
EWWD340DZXEA1
EWWH245DZXEA1
EWWD440DZXSA1
EWWH320DZXSA1
EWWD470DZXEA1
EWWH345DZXEA1
EWWD610DZXSA2
EWWH430DZXSA2
EWWD640DZXSA2
EWWH455DZXSA2
EWWD670DZXEA2
EWWH470DZXEA2
EWWD680DZXEA2
EWWH490DZXEA2
EWWD880DZXSA2
EWWH640DZXSA2
EWWD950DZXEA2
EWWH685DZXEA2
EWWD(H)-DZ COOLING TOWER VERSION
Cooling tower version Model
EWWD530DZXSA1
EWWH380DZXSA1
EWWD570DZXEA1
EWWH405DZXEA1
EWWD700DZXSA1
EWWH460DZXSA1
EWWD740DZXEA1
EWWH480DZXEA1
EWWDC10DZXSA2
EWWH755DZXSA2
EWWDC11DZXEA2
EWWH810DZXEA2
EWWDC14DZXSA2
EWWH920DZXSA2
EWWDC15DZXEA2
EWWH955DZXEA2
Legend:
ELWT
Evaporator outlet water temperature
CLWT Condenser outlet water temperature
2.10 Minimum water content in the system
For correct machine operations and the necessary operating stability, it is important to ensure a minimum water content in
the system. An accumulation tank with suitable volume may be required for this purpose.
The minimum water content must be calculated by considering the following specifications: