background image

EWLP012~065KBW1N

Condenserless water-cooled water chillers

4PW61665-1 – 07.2010

Installation manual

5

C

HECKING

 

THE

 

WATER

 

CIRCUIT

The units are equipped with a water inlet and water outlet for connec-
tion to a chilled water circuit. This circuit must be provided by a
licensed technician and must comply with all relevant European and
national regulations.

Before continuing the installation of the unit, check the following
points:

Additional components not delivered with the unit

1

A circulation pump must be provided in such a way that it
discharges the water directly into the heat exchanger.

2

Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.

3

Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.

Additional water piping delivered with the unit

All additional water piping must be installed on the system according
to the piping diagram as mentioned in the operation manual. The
flowswitch must be connected as described on the wiring diagram.
See also chapter 

"Before starting" on page 7

.

4

A flowswitch must be installed in the water outlet pipe of the
evaporator to prevent the unit from operating at a water flow
which is too low. 

A terminal (X65A) is provided in the switch box for the electrical
connection of the flowswitch (S10L).

5

Shut-off valves must be installed at the unit so that normal
servicing of the water filter can be accomplished without
draining the complete system.

6

Air purge valves must be provided at all high points of the
system. The vents should be located at points which are easily
accessible for servicing.

7

The water filter must be installed in front of the unit for removing
dirt from the water to prevent damage to the unit or blockage of the
evaporator. The water filter must be cleaned on a regular base.

W

ATER

 

QUALITY

 

SPECIFICATIONS

 

A = corrosion 

B = scale

C

ONNECTING

 

THE

 

WATER

 

CIRCUIT

The evaporator is provided with GAS female pipe thread connections
for the water inlet and outlet (refer to the outlook diagram).
Evaporator water connections are to be made in accordance with the
outlook diagram, respecting the water in- and outlet.

If air, moisture or dust gets in the water circuit, problems may occur.
Therefore, always take into account the following when connecting
the water circuit:

1.

Use clean pipes only.

2.

Hold the pipe end downwards when removing burrs.

3.

Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.

The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.

2x Ball valve

1x Water filter

1x Air purge

1x T-joint for air purge

2x Flowswitch pipe

1x Flowswitch
+
1x T-joint

It is very important to install the flowswitch as shown in the
figure. Observe the position of the flowswitch in relation to
the direction of the water flow. If the flowswitch is mounted
in an other position, the unit is not protected properly
against freezing.

evaporator water

circulating 

water

supply water

tendency if 

out of 

criteria

[<20°C]

Items to be controlled

pH

at 25°C

6.8~8.0

6.8~8.0

A + B

Electrical 
conductivity

[mS/m]

at 25°C

<40

<30

A + B

Chloride ion

[mg Cl

/l]

<50

<50

A

Sulfate ion

[mg SO

4

2–

/l]

<50

<50

A

M-alkalinity (pH 4.8)

[mg CaCO

3

/l]

<50

<50

B

Total hardness

[mg CaCO

3

/l]

<70

<70

B

Calcium hardness

[mg CaCO

3

/l]

<50

<50

B

Silica ion

[mg SiO

2

/l]

<30

<30

B

Items to be referred to

Iron

[mg Fe/l]

<1.0

<0.3

A + B

Copper

[mg Cu/l]

<1.0

<0.1

A

Sulfide ion

[mg S

2–

/l]

not detectable

A

Ammonium ion

[mg NH

4

+

/l]

<1.0

<0.1

A

Remaining chloride

[mg Cl/l]

<0.3

<0.3

A

Free carbide

[mg CO

2

/l]

<4.0

<4.0

A

Stability index

A + B

Use a good thread sealant for the sealing of the
connections. The sealing must be able to withstand the
pressures and temperatures of the system, it must also
be resistant to the used glycol in the water.

The exterior of the water pipes must be adequately
protected against corrosion.

4PW61665-1_digital_EN.book  Page 5  Friday, August 27, 2010  2:13 PM

Содержание EWLP020KBW1N

Страница 1: ...TION MANUAL EWLP012KBW1N EWLP020KBW1N EWLP026KBW1N EWLP030KBW1N EWLP040KBW1N EWLP055KBW1N EWLP065KBW1N Condenserless water cooled water chillers 4PW61665 1_digital_EN book Page 1 Friday August 27 2010...

Страница 2: ...arecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet...

Страница 3: ...WLP units Technical specifications 1 Electrical specifications 1 Options and features 1 Options Glycol application for chilled water temperature down to 10 C or 5 C BMS connection MODBUS optional kit...

Страница 4: ...ut of the unit The equipment is not intended for use in a potentially explosive atmosphere INSPECTING AND HANDLING THE UNIT At delivery the unit should be checked and any damage should be reported imm...

Страница 5: ...nd to prevent foreign materials e g mineral oils such as SUNISO and moisture from mixing into the system Vacuum pump use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not f...

Страница 6: ...iquid line sightglass is showing some gas bubbles the rough refrigerant charge is sufficient by fine tuning the additional 10 refrigerant charge weight If the liquid line sightglass is showing flash g...

Страница 7: ...ular base WATER QUALITY SPECIFICATIONS A corrosion B scale CONNECTING THE WATER CIRCUIT The evaporator is provided with GAS female pipe thread connections for the water inlet and outlet refer to the o...

Страница 8: ...uit and cable requirements 1 The electrical power supply to the unit must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipm...

Страница 9: ...040 0 22 EWLP055 0 21 EWLP065 0 20 2 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current...

Страница 10: ...Installation manual 8 EWLP012 065KBW1N Condenserless water cooled water chillers 4PW61665 1 07 2010 NOTES 4PW61665 1_digital_EN book Page 8 Friday August 27 2010 2 13 PM...

Страница 11: ...water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency shut down Switch off the ci...

Страница 12: ...4PW61665 1 07 2010 Copyright 2010 Daikin 4PW61665 1_digital_EN book Page 1 Friday August 27 2010 2 13 PM...

Отзывы: