background image

EWLD120~540MBYNN

Condenserless water-cooled water chillers

4PW22687-1

Operation manual

18

Symptom 3: The unit does not start and the ON LED does not light up

3

Symptom 4: One of the circuits does not start up

Symptom 5: One of the following safety devices is activated

5.1

5.2

5.3

5.4

5.5

5.6

5.7

5.8

Symptom 6: Unit stops soon after operation

Symptom 7: Unit runs continuously and the water temperature remains 
higher than the temperature set on the controller

Symptom 8: Excessive noises and vibrations of the unit

Symptom 9: The display shows 

 

 (only in a DICN system)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

All circuits are in failure mode.

Refer to Symptom 5: One of the 
following safety devices is activated.

One of the following safety devices is 
activated:

• flowswitch (S8L,S9L)
• Emergency stop

Refer to Symptom 5: One of the 
following safety devices is activated.

The ON LED is broken.

Contact your local dealer.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

One of the following safety devices is 
activated:

• Compressor thermal protector (Q*M)
• Overcurrent relay (K*S)
• Discharge thermal protector (S*T)
• Low pressure
• High pressure switch (S*PH)
• Reverse phase protector (R*P)
• Freeze-up

Check on the controller and refer to 
Symptom 5: One of the following 
safety devices is activated.

The anti-recycling timer is still active.

The circuit can only start up after 
approximately 10 minutes.

The guard timer is still active.

The circuit can only start up after 
approximately 1 minute.

The circuit is limited to 0%.

Check the "enable/disable capacity 
limitation" remote contact.

Symptom 5.1:  Overcurrent relay of compressor

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

RESET

Push the blue button on the over-
current relay inside the switch box 
and reset the controller.

Symptom 5.2:  Low pressure 

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Dirty evaporator.

Clean the evaporator, or call your 
local dealer

Low pressure safety setting too high.

Refer to the installation manual 
“Customization in the service menu”, 
paragraph “Setting of the minimum 
outlet water temperature” for correct 
values.

flowswitch is not working or no water 
flow.

Check the flowswitch and the water 
pump.

RESET

After pressure rise, this safety resets 
automatically, but the controller still 
needs to be reset.

Symptom 5.3:  High-pressure switch

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Inlet air temperature is too high.

The air temperature measured at the 
inlet of the condenser may not 
exceed 43°C.

RESET

After finding the cause, push the 
button on the high-pressure switch 
housing and reset the controller.

Symptom 5.4:  Reverse phase protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Two phases of the power supply are 
connected in the wrong phase 
position.

Invert two phases of the power 
supply (by licensed electrician).

One phase is not connected 
properly.

Check the connection of all phases.

RESET

After inverting two phases or fixing 
the power supply cables properly, 
the protector is reset automatically, 
but the controller still needs to be 
reset.

Symptom 5.5:  Discharge thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit is working outside the operation 
range.

Check the operation condition of the 
unit.

RESET

After temperature decrease, the 
thermal protector resets 
automatically but the controller still 
needs to be reset.

Symptom 5.6:  flowswitch is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

No water flow.

Check the water pump.

RESET

After finding the cause, the 
flowswitch is reset automatically, but 
the controller still needs to be reset.

Symptom 5.7:  Freeze-up protection is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow too low.

Increase the water flow.

Inlet temperature to the evaporator is 
too low.

Increase the inlet water temperature.

flowswitch is not working or no water 
flow.

Check the flowswitchflowswitch and 
the water pump.

RESET

After temperature increase the 
freeze-up is reset automatically, but 
the circuit controller needs to be 
reset.

Symptom 5.8:  Compressor thermal protector is activated

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Compressor motor coil temperature 
too high.

Compressor is not cooled sufficiently 
by the refrigerant medium.

RESET

After temperature decrease the 
thermal protector is reset 
automatically, but the circuit 
controller needs to be reset.

If the protector is activated 
frequently, call your local dealer.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The schedule timer is activated and 
is in off mode.

Work according to the settings in the 
schedule timer or disable the 
schedule timer.

One of the safety devices is 
activated. 

Check safety devices (refer to 
Symptom 5: One of the following 
safety devices is activated).

Voltage is too low.

Test the voltage in the supply panel 
and, if necessary, in the electrical 
compartment of the unit (voltage 
drop due to supply cables is too 
high).

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The temperature setting on the 
controller is too low.

Check and adjust the temperature 
setting.

The heat production in the water 
circuit is too high.

The cooling capacity of the unit is too 
low. Call your local dealer.

Water flow is too high.

Recalculate the water flow.

The circuit is limited.

Check the "enable/disable capacity 
limitation" remote contact.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit has not been fixed properly.

Fix the unit as described in the 
installation manual.

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The adresses set on the PCB or 
controller are wrong.

Make sure to set the correct 
adresses. Refer to "Setting the 
adresses" in the installation manual.

Содержание EWLD120MBYNN

Страница 1: ...OPERATION MANUAL EWLD120MBYNN EWLD170MBYNN EWLD240MBYNN EWLD260MBYNN EWLD340MBYNN EWLD400MBYNN EWLD480MBYNN EWLD500MBYNN EWLD540MBYNN Condenserless water cooled water chillers...

Страница 2: ...d water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Before starting up the unit for the first tim...

Страница 3: ...0 Condensor refer to engeneering specifications as published by the supplier of your remote condenser Evaporator Type brased plate heatexchanger Qty x model 2x AC250EQ NP128 1x AC250EQ NP128 1x AC250...

Страница 4: ...sor 14 Digital display controller 2 Evaporator 15 Emergency stop 3 Switchbox 16 Power supply intake 4 Compressor switchbox 17 Field wiring intake 5 Charge valve 18 Holes for lifting 6 Safety valve 19...

Страница 5: ...orator The main function of the evaporator is to take heat from the water that flows through it This is done by turning the liquid refrigerant coming from the condenser into gaseous refrigerant Water...

Страница 6: ...omes too high If this occurs shut down the unit and contact your local dealer High pressure switch Each circuit is protected by two high pressure switches S PH which measure the condenser pressure pre...

Страница 7: ...circuit 2 BEFORE OPERATION Checks before initial start up After the installation of the unit check the following before switching on the circuit breaker 1 Field wiring Make sure that the field wiring...

Страница 8: ...he switch boxes may only be opened by a licensed electrician for maintenance purposes 3 To prevent the evaporator from freezing and to avoid damage to the LCD displays of the digital controller never...

Страница 9: ...an initialization cycle is started Once all the timers have reached zero the unit starts up When the remote ON OFF control parameter is set to YES the following table applies 2 If the water chiller do...

Страница 10: ...available if voltage and current transmitters are installed This readout menu provides information concerning the voltage and the compressor current 7 Press the h key to enter the next screen of the...

Страница 11: ...s provided by the different menus In the following chapter you will find how you can set up and configure the unit using the various menu functions All menus are directly accessible using the correspo...

Страница 12: ...ot a password is needed to enter the setpoints menu To enter the service menu only a qualified installer is allowed to access this menu 2 5 4 4 2 2 1 2 2 To check the actual value of the general softw...

Страница 13: ...ther or not the discharge thermal protector or the compressor thermal protector are activated for circuit 1 To check the status of the high pressure switch the reverse phase protector and the overcurr...

Страница 14: ...to a failure circuit 1 will start up instead In the automatic mode the number of hours indicated on the display is the maximum difference between the running hours of both circuits This value is impor...

Страница 15: ...en Defining free cooling The screen of the usersettings menu allows the user to control a 3 way water valve when the unit is in free cooling state To make this possible a changeable digital output has...

Страница 16: ...the water flow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD refer to the pump contr...

Страница 17: ...which contains the following information the time and date 2 Press h to consult the first screen This screen contains information about the unit name and the refrigerant used 3 Press h to consult the...

Страница 18: ...en a safety device was activated stop the unit and find out why the safety device was activated before resetting it Under no circum stances safety devices may be bridged or changed to a value other th...

Страница 19: ...t the inlet of the condenser may not exceed 43 C RESET After finding the cause push the button on the high pressure switch housing and reset the controller Symptom 5 4 Reverse phase protector is activ...

Страница 20: ...pecifications of the water quality Water filters Make sure to clean the waterfilter in front of the evaporator water inlet once every 4 months Check the filter for any possible damage and make sure th...

Страница 21: ...t working The diagram and table below show the default value and the upper and lower limits of the floating setpoint parameters on the evaporator INLET CONTROL Default value Lower limit Upper limit St...

Страница 22: ...ttings of groups and work similar as following example settings for group 1 ANNEX IV Free cooling working Free cooling on ambient temperature Free cooling on difference between inlet water evaporator...

Страница 23: ...2 2 q h q q g h h h g h g h g h g h g h g h g g h g h g h g h g h g h g h g h g h g h g h g h h g g g 2 f 4 4 2 5 4 4 2 4 4 4 4 4 4 4 4 4 4 0 4 4 4 4 g h g h g h q h p 2 6 g h g h 0 7 g h 3 3 2 2 2 1...

Страница 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22687 1...

Отзывы: