4/7
Breadcrumb
Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.6.3.5.2
[5-06]
Amp. limits for DI
Limit DI2
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.3
[5-07]
Amp. limits for DI
Limit DI3
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.4
[5-08]
Amp. limits for DI
Limit DI4
R/W
0~50 A, step: 1 A
50 A
A.6.3.6.1
[5-09]
kW limits for DI
Limit DI1
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2
[5-0A]
kW limits for DI
Limit DI2
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3
[5-0B]
kW limits for DI
Limit DI3
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4
[5-0C]
kW limits for DI
Limit DI4
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.7
[4-01]
R/W
0~2
0: None
2: BUH
└─
Averaging time
A.6.4
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Ext amb. sensor offset
A.6.5
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Boiler efficiency
A.6.A
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
└─
Emergency
A.6.C
R/W
0: Manual
1: Automatic
└─
Overview settings
A.8
[0-00]
35°C
A.8
[0-01]
45°C
A.8
[0-02]
15°C
A.8
[0-03]
-10°C
A.8
[0-04]
8°C
A.8
[0-05]
12°C
A.8
[0-06]
35°C
A.8
[0-07]
20°C
A.8
[0-0B]
55°C
A.8
[0-0C]
60°C
A.8
[0-0D]
15°C
A.8
[0-0E]
-10°C
A.8
[1-00]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[1-01]
R/W
10~25°C, step: 1°C
15°C
A.8
[1-02]
R/W
[9-01]~[9-00], step: 1°C
45°C
A.8
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
35°C
A.8
[1-04]
R/W
0: Disabled
1: Enabled
A.8
[1-05]
1
A.8
[1-06]
R/W
10~25°C, step: 1°C
20°C
A.8
[1-07]
R/W
25~43°C, step: 1°C
35°C
A.8
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
A.8
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
18°C
A.8
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8
[2-00]
5
A.8
[2-01]
1
A.8
[2-02]
23
A.8
[2-03]
60
A.8
[2-04]
40
A.8
[2-05]
R/W
4~16°C, step: 1°C
16°C
A.8
[2-06]
R/W
0: Disabled
1: Enabled
A.8
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[3-00]
R/W
0: No
1: Yes
A.8
[3-01]
0
A.8
[3-02]
1
A.8
[3-03]
4
A.8
[3-04]
2
A.8
[3-05]
1
A.8
[3-06]
R/W
18~30°C, step: A.3.2.4
30°C
A.8
[3-07]
R/W
12~18°C, step: A.3.2.4
16°C
A.8
[3-08]
R/W
25~35°C, step: A.3.2.4
35°C
A.8
[3-09]
R/W
15~25°C, step: A.3.2.4
15°C
A.8
[4-00]
R/W
0~2
0: Disabled
1: Enabled
What is the maximum desired room temperature in heating?
What is the minimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
What is the BUH operation mode?
Is auto restart of the unit allowed?
--
--
--
--
--
--
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
--
--
--
--
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
--
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
--
--
--
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
--
--
--
--
--
--
--
--
--
Priority
4P478618-1B - 2017.06
(*1) EWYQ*_(*2) EWAQ*