25
EWAQ+EWYQ009~0 EWAQ+EWYQ009~013ACW1
Packaged air-cooled water chillers and packaged
reversible air to water heatpumps
4PW51587-1A
T
ECHNICAL
SPECIFICATIONS
General
Electrical specifications
V3 models (1~)
W1 models (3N~)
EWAQ009 EWAQ010 EWAQ011 EWYQ009 EWYQ010 EWYQ011 EWAQ009 EWAQ011 EWAQ013 EWYQ009 EWYQ011 EWYQ013
Nominal capacity
• cooling
Refer to the Technical Data
Refer to the Technical Data
• heating
Refer to the Technical Data
Refer to the Technical Data
Dimensions H x W x D
1418 x 1435 x 382
1418 x 1435 x 382
Weight
• machine weight
180 kg
180 kg
• operation weight
185 kg
185 kg
Connections
• water inlet/outlet
G 5/4" FBSP
(a)
• water drain
hose nipple
hose nipple
• refrigerant liquid side
Ø9.5 mm (3/8 inch)
Ø9.5 mm (3/8 inch)
• refrigerant gas side
Ø15.9 mm (5/8 inch)
Ø15.9 mm (5/8 inch)
Expansion vessel
• volume
10 l
10 l
• maximum working
pressure (MWP)
3 bar
3 bar
Pump
• type
water cooled
water cooled
• no. of speed
2
2
Sound pressure level
(b)
• heating
—
—
—
51 dBA
51 dBA
51 dBA
—
—
—
51 dBA
51 dBA
52 dBA
• cooling
51 dBA
51 dBA
51 dBA
51 dBA
51 dBA
51 dBA
51 dBA
51 dBA
52 dBA
51 dBA
51 dBA
52 dBA
Internal water volume
4 l
4 l
Pressure relief valve
water circuit
3 bar
3 bar
Operation range - water side
• heating
—
+25~+50°C
—
+25~+50°C
• cooling
+5~+22°C
+5~+22°C
+5~+22°C
+5~+22°C
Operation range - air side (RH: 85%)
• heating
—
–15~+35°C
—
–15~+35°C
• cooling
+10~+46°C
+10~+46°C
+10~+46°C
+10~+46°C
(a) FBSP = Female British Standard Pipe
(b) At 1 m in front of the unit (free field condition)
V3 models (1~)
W1 models (3N~)
Standard unit (power supply via unit)
• power supply
230 V 50 Hz 1P
400 V 50 Hz 3P
• nominal running current
—
5.8 A