D - KIMAC00512-09EN - 37/40
Troubleshooting chart
PROBLEM
POSSIBLE CAUSES
POSSIBLE CORRECTIVE STEPS
Compressor will
not run
1. Main power switch open.
2. Unit system switch open.
3. Circuit switch in pump-down position.
4. Evaporator flow switch not closed.
5. Circuit breakers open.
6. Fuse blown or circuit breakers tripped.
7. Unit phase voltage monitor not satisfied.
8. Compressor overload tripped.
9. Defective compressor contactor or
contactor coil.
10. System shut down by safety devices.
11. No cooling required.
12. Motor electrical trouble.
13. Loose wiring.
1. Close switch.
2. Check unit status on Control Panel. Close
switch.
3. Check circuit status on Control Panel.
Close switch.
4. Check unit status on Control Panel. Close
switch.
5. Close circuit breakers.
6. Check electrical circuits and motor
windings for shorts or grounds.
Investigate for possible overloading.
Check for loose or corroded connections.
Reset breakers or replace fuses after fault
is corrected.
7. Check unit power wiring to unit for correct
phasing. Check voltage.
8. Overloads are manual reset. Reset
overload at button on overload.
Clear alarm on Microprocessor.
9. Check wiring. Repair or replace contactor.
10. Determine type and cause of shutdown
and correct problem before attempting to
restart.
11. Check control settings. Wait until unit calls
for cooling.
12. See 6, 7, 8 above.
13. Check circuits for voltage at required
points. Tighten all power wiring terminals.
Compressor
Overload Relay
Tripped or
Circuit Breaker
Trip or Fuses
Blown
1. Low voltage during high load condition.
2. Loose power wiring.
3. Power line fault causing unbalanced
voltage.
4. Defective or grounded wiring in the motor.
5. High discharge pressure.
1. Check supply voltage for excessive
voltage drop.
2. Check and tighten all connections.
3. Check supply voltage.
4. Check motor and Replace if defective.
5. See Corrective steps for high discharge
pressure.
Compressor
noisy or
vibrating
1. Compressor internal problem.
2. Oil injection not adequate.
1. Contact DAIKIN.
2. Contact DAIKIN.
Compressor will
not load or
unload
1. Defective capacity control.
2. Unloader mechanism defective.
3. Control solenoids defective.
1. See capacity control section.
2. Replace.
3. Replace.