6 Electrical installation
Installation manual
17
EWAA004~008D2 + EWYA004~008D2
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688014-1A – 2022.05
In case of preferential kWh rate power supply
Preferential kWh
rate power supply
Wires: 1N+GND
Maximum running current: Refer to name
plate on unit.
Separate normal
kWh rate power
supply
Wires: 1N
Maximum running current: 6.3 A
Preferential kWh
rate power supply
contact
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply
contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free
contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
[9.8]
Benefit kWh power supply
1
Connect the preferential kWh rate power supply.
N
N
L N
N
N PE
N
Q1DI
N
L.
M1
X
N
N
N
N
N
N.
M1
X
N
.
M1
X
N
N
N
N
N
N
N
N
1N~
N
1N~, 50 Hz,
220-240 V AC
N
N
X1M
N
L N
1N~
180°
2
If necessary, connect the separate normal kWh rate power
supply.
INFORMATION
Some types of preferential kWh rate power supply require
a separate normal kWh rate power supply to the outdoor
unit. This is required in the following cases:
▪ if the preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the hydro module of the
outdoor unit is allowed at the preferential kWh rate
power supply when active.
5.
M2
X
6.
M2
X
L N
1N~, 50 Hz,
230 V AC, 6.3 A
180°
6
5
X2M
3
Connect the preferential power supply contact.
X5M.10
S1S
X5M.9
9
10
X5M
180°
4
In case of a separate normal kWh rate power supply,
disconnect X11Y from X11YA, and connect X11Y to X11YB.