6 Electrical installation
Installation manual
15
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620240-1 – 2020.06
In case of preferential kWh rate power supply
Preferential kWh
rate power supply
Wires: 1N+GND, OR 3N+GND
Maximum running current: Refer to name
plate on unit.
Separate normal
kWh rate power
supply
Wires: 1N
Maximum running current: 6.3 A
Preferential kWh
rate power supply
contact
Wires: 2×(0.75~1.25 mm²)
Maximum length: 50 m.
Preferential kWh rate power supply
contact: 16 V DC detection (voltage
supplied by PCB). The voltage-free
contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
[9.8]
Benefit kWh power supply
1
Open the service cover. See
9].
2
Connect the preferential kWh rate power supply (1N~or 3N~
depending on model, see name plate).
N
L N PE
Q1DI
X1M.L
X1M.L1
X1M.L2
X1M.L3
X1M.N
X1M.N
X1M.
X1M.
L3
L2
L1
N PE
Q1DI
1N~
3N~
OR
1N~, 50 Hz,
220-240 V AC
3N~, 50 Hz,
380-415 V AC
X1M
OR
1N~
3N~
L1 L2 L3 N
L N
3
If necessary, connect the separate normal kWh rate power
supply.
INFORMATION
Some types of preferential kWh rate power supply require
a separate normal kWh rate power supply to the outdoor
unit. This is required in the following cases:
▪ if the preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the hydro module of the
outdoor unit is allowed at the preferential kWh rate
power supply when active.
N
L
X2M.6
X2M.5
1N~, 50 Hz,
230 V AC, 6.3 A
6
5
X2M
4
Connect the preferential power supply contact.
X5M.10
X5M.9
S1S
9 10
X5M
5
Disconnect X11Y from X11YA, and connect X11Y to X11YB.